Specifications

Network Frequency
50/60 Hz
Network Type
AC
Breaking Capacity Code
N1
Product Or Component Type
circuit breaker
Product Name
MasterPact MTZ2
Range
Masterpact
Utilisation Category
category B
Suitability For Isolation
yes IEC 60947-2
Poles Description
3P
Device Application
protection
Device Short Name
MTZ2 12 N1

Complementary

[Ics] Rated Service Breaking Capacity
42 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 42 kA 440 V AC 50/60 Hz IEC 60947-2 || 42 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 42 kA 660/690 V AC 50/60 Hz IEC 60947-2
Line Rated Current
1250 A 40 °C
Connection Pitch
115 mm
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz IEC 60947-2
Mounting Support
base plate || rails
Circuit Breaker Ct Rating
1250 A
Maximum Breaking Time
25-25 ms
Depth
300 mm
Control Type
push-button
Maximum Closing Response Time
70 ms
Mounting Mode
fixed
Breaking Capacity
42 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
[Icm] Rated Short-Circuit Making Capacity
88 kA 220/415 V AC 50/60 Hz || 88 kA 440 V AC 50/60 Hz || 88 kA 500/525 V AC 50/60 Hz || 88 kA 660/690 V AC 50/60 Hz
Electrical Durability
10000 cycles 440 V AC 50/60 Hz IEC 60947-2 || 10000 cycles 690 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage
1000 V AC 50/60 Hz IEC 60947-2
Mechanical Durability
25000 cycles with periodic preventive maintenance IEC 60947-2
Height
352 mm
Width
422 mm
[Uimp] Rated Impulse Withstand Voltage
12 kVIEC 60947-2
[Icw] Rated Short-Time Withstand Current
42 kA 0.5 s IEC 60947-2 || 42 kA 1 s IEC 60947-2 || 22 kA 3 s IEC 60947-2

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1607009EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1607009EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
ASEFA
Ambient Air Temperature For Operation
-25-70 °C
Standards
IEC 60947-2 || IEC 60364-8-1
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-40-85 °C

Modele CAD