Schneider Electric
LV848313
1 / 1
- Country of Origin
- FR
- Part Number
- LV848313
- Tariff Code
- 85362090
- EAN
- 3606480808999
- UNSPSC
- 39121601
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Specifications
- Network Frequency
- 50/60 Hz
- Network Type
- AC
- Breaking Capacity Code
- H2
- Product Or Component Type
- circuit breaker
- Product Name
- MasterPact MTZ2
- Range
- Masterpact
- Utilisation Category
- category B
- Suitability For Isolation
- yes IEC 60947-2
- Poles Description
- 3P
- Device Application
- protection
- Device Short Name
- MTZ2 32 H2
Complementary
- [Ics] Rated Service Breaking Capacity
- 100 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 100 kA 440 V AC 50/60 Hz IEC 60947-2 || 85 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 85 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Line Rated Current
- 3200 A 40 °C
- Connection Pitch
- 115 mm
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Mounting Support
- rails || base plate
- Circuit Breaker Ct Rating
- 3200 A
- Maximum Breaking Time
- 25-25 ms
- Depth
- drawout circuit breaker without chassis 300 mm || drawout circuit breaker with chassis 403 mm
- Control Type
- push-button
- Maximum Closing Response Time
- 70 ms
- Mounting Mode
- drawout
- Breaking Capacity
- 100 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 85 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 85 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- [Icm] Rated Short-Circuit Making Capacity
- 220 kA 220/415 V AC 50/60 Hz || 220 kA 440 V AC 50/60 Hz || 187 kA 500/525 V AC 50/60 Hz || 187 kA 660/690 V AC 50/60 Hz
- Electrical Durability
- AC-3 6000 cycles 440/690 V AC 50/60 Hz IEC 60947-3 || 2500 cycles 690 V AC 50/60 Hz IEC 60947-2 || 5000 cycles 440 V AC 50/60 Hz IEC 60947-2 || AC-23A 2500 cycles 690 V AC 50/60 Hz IEC 60947-3 || AC-23A 5000 cycles 440 V AC 50/60 Hz IEC 60947-3
- [Ui] Rated Insulation Voltage
- 1000 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability
- 20000 cycles with periodic preventive maintenance IEC 60947-2
- Height
- drawout circuit breaker without chassis 300 mm || drawout circuit breaker with chassis 439 mm
- Width
- drawout circuit breaker without chassis 378 mm || drawout circuit breaker with chassis 441 mm
- Integral Instant Protection
- 171-209 kA
- [Uimp] Rated Impulse Withstand Voltage
- 12 kVIEC 60947-2
- [Icw] Rated Short-Time Withstand Current
- 85 kA 0.5 s IEC 60947-2 || 85 kA 1 s IEC 60947-2 || 75 kA 3 s IEC 60947-2
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1607009EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI1607009EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- ASEFA
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- IEC 60947-2 || IEC 60364-8-1
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -40-85 °C
Modele CAD
traceparts
Pobierz