- [Uc] Control Circuit Voltage
- 110...230 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- 500 V AC
- Thermal Protection Adjustment Range
- 0.18-2.4 A
- Product Or Component Type
- reversing ultra-compact starter
- Product Name
- TeSys Hybrid
- Thermal Overload Class
- class 10A IEC 60947-4-2
- Motor Power Kw
- 0.37 kW 220 V AC 0.65 || 0.37 kW 230 V AC 0.65 || 0.75 kW 380 V AC 0.65 || 0.75 kW 400 V AC 0.65 || 0.75 kW 415 V AC 0.65 || 0.75 kW 440 V AC 0.65 || 1.1 kW 500 V AC 0.65
- Range
- TeSys
- Motor Starter Type
- direct on line
- [Ie] Rated Operational Current
- 2.4 A 500 V AC-51 || 2.4 A 500 V AC-53A || 2.4 A 500 V AC-51 mounting side by side || 2.4 A 500 V AC-53A mounting side by side
- Poles Description
- 3P
- Safety Reliability Data
- SFF = 99 % stop function || SFF = 99 % motor protection || MTTFd = 289 years stop function || MTTFd = 273 years motor protection || PFHd = 6.82E-9 1/h stop function
- Maximum Horse Power Rating
- 0.5 hp 200 V AC || 0.5 hp 230 V AC || 1 hp 460 V AC
- Device Short Name
- LZ8H
- Safety Level