Schneider Electric
RLF36200U31A
1 / 1
Opis
Końcówka Serii
PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard Trip with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT R circuit breakers are available in 2, 3, and 4-pole unit mount and I-Line construction (I-Line construction is available for 1000A and 1200A rated circuit breakers only). This unit has a busbar connection. This PowerPacT P, 2000A, 3 pole, circuit breaker has an interrupting rating of 50kA at 600VAC. The circuit breaker has a continuous current rating of 80%. PowerPacT R circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.- Country of Origin
- US
- Part Number
- RLF36200U31A
- Tariff Code
- 8536200020
- EAN
- 39121601
- UNSPSC
- 39121601
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- IP40
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206034EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206034EN
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts product
Complementary
- Mounting Mode
- unit mount busbar)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL2500RK
- [Ics] Rated Service Breaking Capacity
- 65 kA 240 V AC 50/60 Hz IEC 60947-2 || 45 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Trip Unit Technology
- electronic, standard, MicroLogic 3.0, LI
- Trip Unit Name
- MicroLogic 3.0
- Height
- 16.24 in
- [Ue] Rated Operational Voltage
- 600 V AC 50/60 Hz UL 489
- Tightening Torque
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Mounting Support
- busbar
- Breaking Capacity Code
- L
- Local Signalling
- alarm 1 LED yellow)long-time pick up)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- busbar connection, line || busbar connection, load
- Net Weight
- 52 lb(US)
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- operating handle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 35 mm
- Line Rated Current
- 2000-2000 A
- Utilisation Category
- category A
- Continuous Current Rating
- 80 %
- Breaking Capacity
- AIR 125 kA 240 V AC 50/60 Hz UL 489 || AIR 100 kA 480 V AC 50/60 Hz UL 489 || AIR 50 kA 600 V AC 50/60 Hz UL 489 || Icu 125 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 85 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Poles Description
- 3P
- Quantity Per Set
- 1
- Awg Gauge
- AWG 3/0...750 kcmil aluminium/copper
- Width
- 16.53 in
- Depth
- 14.49 in
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact R
- Range
- PowerPact
- Device Application
- distribution
Dokumenty
Data Sheet
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne