- [Us] Rated Supply Voltage
- 380...415 V AC 50/60 Hz
- Safety Reliability Data
- MTTFd = 125.5 years || B10d = 120000
- Maximum Electrode Voltage
- 12 V AC
- Cable Capacitance
- 1 nF HS (High Sensitivity) probe cable || 2.2 nF St (Standard Sensitivity) probe cable || 4.7 nF LS (Low Sensitivity) probe cable
- Measurement Error
- < 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
- Maximum Cable Distance Between Devices
- 1000 m probe and delay
- Output Contacts
- 2 C/O
- Contacts Material
- cadmium free
- Sensitivity Scale
- 5...100 kOhm St (Standard Sensitivity)
- Net Weight
- 0.1 kg
- Maximum Switching Voltage
- 250 V AC
- Maximum Electrode Current
- 1 mA
- Connections - Terminals
- screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
- Overvoltage Category
- III IEC 60664-1
- Insulation
- between supply and measurement
- Supply Voltage Limits
- 323-456.5 V AC
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Nominal Output Current
- 8 A
- Mechanical Durability
- 10000000 cycles
- Maximum Supply Current For Sensors
- 1 mA
- Housing Material
- self-extinguishing plastic
- Mounting Position
- any position
- Width
- 22.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Sensitivity Adjustment
- 5-100 %
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 0.6 s
- Repeat Accuracy
- +/- 2 % time delay