This Harmony RPM power plug-in relay has a coil control voltage of 48V DC and has 2 changeover contacts DPDT (double pole double throw) with a rating of 15A. It has large choice of number of contacts for high rated current use. It helps to reduce the size of enclosures and increases machine reliability, you can mount nearly everywhere. Plug in type enables easy installation and maintenance. Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs). 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Country of Origin
CN
Part Number
RPM21ED
Tariff Code
85364190
EAN
3389119401838
UNSPSC
39122326
Metody płatności:
Najlepsza oferta od:
GBZaufany dostawca Automa.Net
Dostępność:
9 szt.
W magazynie
Zaktualizowano: 30-04-2024
Szacowany czas dostawy:
Na zapytanie
Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Fabrycznie Nowe, Zapieczętowane - Nowy, nieużywany, nieotwarty, nieuszkodzony przedmiot w oryginalnym opakowaniu zapieczętowanym przez producenta.
Łącznie 10 części w magazynie od 2 dostawców
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja

Dostępne Oferty (1)

RPM21ED product image
Schneider Electric

RPM21ED

Stan produktu:
Nowy, Rynek wtórny
Dostępność:
1 szt.
W magazynie
Zaktualizowano: 08-11-2024
Oferta od:
DEZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
Gwarancja:
12 miesięcy
1
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€4.02

Specifications

Utilisation Coefficient
20 %
[Uc] Control Circuit Voltage
48 V DC
Range Of Product
Harmony Electromechanical Relays
Product Or Component Type
plug-in relay
Status Led
without
Control Type
lockable test button
Series Name
Power
Contacts Type And Composition
2 C/O
Device Short Name
RPM
[Ithe] Conventional Enclosed Thermal Current
15 A -40-55 °C

Contractual warranty

Warranty
18 months

Complementary

Maximum Switching Capacity
3750 VA || 420 W
Safety Reliability Data
B10d = 100000
Operating Rate
<= 1200 cycles/hour under load || <= 18000 cycles/hour no-load
Protection Category
RT I
Test Levels
level A
Electrical Durability
100000 cycles resistive
Contacts Material
AgNi
Shape Of Pin
flat
Reset Time
20 ms at nominal voltage
Net Weight
0.036 kg
Maximum Switching Voltage
250 V IEC
Average Resistance
2560 Ohm at 20 °C +/- 10 %
Device Presentation
complete product
Average Coil Consumption
0.85 W
Rated Operational Voltage Limits
38.4...52.8 V DC
Pollution Degree
3
[Ie] Rated Operational Current
15 A 277 V AC) UL || 15 A 28 V DC) UL || 15 A 250 V AC) NO IEC || 15 A 28 V DC) NO IEC || 7.5 A 250 V AC) NC IEC || 7.5 A 28 V DC) NC IEC
[Ui] Rated Insulation Voltage
250 V IEC || 300 V CSA || 300 V UL
Mechanical Durability
10000000 cycles
Operating Position
any position
Operating Time
20 ms at nominal voltage
Load Current
15 A 250 V AC || 15 A 28 V DC
Drop-Out Voltage Threshold
>= 0.1 Uc DC
[Uimp] Rated Impulse Withstand Voltage
4 kV 1.2/50 µs
Minimum Switching Capacity
170 mW 10 mA, 17 V

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1406038EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
UL || CSA || EAC
Standards
EN/IEC 61810-1 || CSA C22.2 No 14 || UL 508
Ambient Air Temperature For Operation
-40-55 °C
Dielectric Strength
1500 V AC between contacts with micro disconnection || 2000 V AC between coil and contact with reinforced || 2000 V AC between poles with basic
Vibration Resistance
3 gn +/- 1 mm 10-150 Hz)5 cycles in operation || 5 gn +/- 1 mm 10-150 Hz)5 cycles not operating
Shock Resistance
15 gnin operation || 30 gnnot operating
Ip Degree Of Protection
IP40 conforming to EN/IEC 60529
Ambient Air Temperature For Storage
-40-85 °C

Modele CAD

traceparts
traceparts
Pobierz