- Utilisation Coefficient
- 20 %
- Maximum Switching Capacity
- 2500 VA AC || 300 W DC
- Safety Reliability Data
- B10d = 100000
- [Uc] Control Circuit Voltage
- 230 V AC 50/60 Hz
- Insulation Resistance
- 1000 MOhm at 500 V DC
- Operating Rate
- <= 1800 cycles/hour under load || <= 18000 cycles/hour no-load
- Torque Value
- 0.8 N.m || 7.0 lbf.in
- Protection Category
- RT I
- Test Levels
- level A group mounting
- Contacts Material
- silver alloy (AgSnO2In2O3)
- Pollution Degree
- 2
- Reset Time
- 20 ms
- Shock Resistance
- 20 gn in operation || 100 gn not in operation
- Dielectric Strength
- 1000 V AC between contacts with micro disconnection || 1300 V between terminals and base with basic insulation || 3000 V between terminals and LTB area with basic insulation || 5000 V AC between coil and contact with reinforced insulation
- Status Led
- with
- Net Weight
- 0.058 kg
- Colour Of Cover
- transparent
- Maximum Switching Voltage
- 250 V
- Device Presentation
- complete product
- Electrical Insulation Class
- class F
- Connections - Terminals
- connector, 1 x 0.25...1 x 2.5 mm² AWG 22...AWG 14) flexible with cable end || connector, 2 x 0.25...2 x 1 mm² AWG 22...AWG 17) flexible with cable end || connector, 1 x 0.5...1 x 2.5 mm² AWG 20...AWG 14) solid without cable end || connector, 2 x 0.5...2 x 1.5 mm² AWG 20...AWG 16) solid without cable end
- Average Coil Consumption
- 0.96 VA AC 50-60 Hz
- [Ie] Rated Operational Current
- 10 A 30 V DC) UL || 10 A 30 V DC) IEC || 10 A 250 V AC) IEC || 10 A 250 V AC) UL
- [Ui] Rated Insulation Voltage
- 250 V IEC
- Electrical Durability
- 100000 cycles resistive
- Mechanical Durability
- 10000000 cycles
- Resistance
- 23500 Ohm +/- 15 %
- Mounting Position
- any position
- Overvoltage Category
- III
- Load Current
- 10 A
- Drop-Out Voltage Threshold
- >= 0.3 Uc AC
- Minimum Switching Capacity
- 500 mW at 100 mA, 5 V DC
- Operating Time
- 20 ms
- Contact Resistance
- 100 mOhm