- Terminals Description Iso N°1
- (13-14)NO || (21-22)NC
- Short-Circuit Protection
- 6 A cartridge fuse gG
- Operating Force
- 3.5 N NO changing electrical state || 4.5 N NC changing electrical state
- Operating Travel
- 1 mm NO changing electrical state) || 2 mm NC changing electrical state) || 3.5 mm total travel)
- Contacts Material
- silver alloy (Ag/Ni)
- Positive Opening
- with EN/IEC 60947-5-1 appendix K
- Net Weight
- 0.022 kg
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV EN/IEC 60947-1
- Cad Overall Height
- 18 mm
- Electrical Durability
- 1000000 cycles, AC-15 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
- [Ui] Rated Insulation Voltage
- 250 V 3)EN/IEC 60947-1
- [Ie] Rated Operational Current
- 3 A 120 V, AC-15, B300 EN/IEC 60947-5-1 || 1.5 A 240 V, AC-15, B300 EN/IEC 60947-5-1 || 0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1 || 0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1
- Mechanical Durability
- 2000000 cycles
- Operating Position
- any position
- Electrical Reliability
- λ = 10exp(-8) 5 V 1 mA with confidence level of 90 % IEC 60947-5-4
- Cad Overall Width
- 18 mm
- Cad Overall Depth
- 57 mm