- Height
- 146-146 mm
- Maximum Operating Rate
- 10 cyc/mn for maximum durability
- [Ui] Rated Insulation Voltage
- 250 VEN/IEC 60947-1 signalling circuit
- Short-Circuit Protection
- 10 A cartridge fuse gG (gl)
- Positive Opening
- with NC contact
- Load Factor
- 1
- Minimum Actuation Speed
- 0.01 m/s
- [Ie] Rated Operational Current
- 0.55 A 125 V, DC-13, Q300 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 || 3 A 120 V, AC-15, B300 EN/IEC 60947-5-1 || 1.5 A 240 V, AC-15, B300 EN/IEC 60947-5-1
- Signalling Circuit Consumption
- 7 mA
- Minimum Actuator Force For Extraction
- 20 N
- Mechanical Durability
- 1000000 cycles
- Maximum Actuation Speed
- 0.5 m/s
- Body Material
- zamak
- [Ithe] Conventional Enclosed Thermal Current
- 6 A
- Safety Reliability Data
- B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
- Power Consumption In Va
- 10 VA inrush || 10 VA sealed
- Supply Voltage Type
- AC/DC
- Width
- 98 mm
- Actuator Forcible Withdrawal Rtc
- 2000 N
- Depth
- 44 mm
- Head Material
- zamak
- Signalling Circuit Type
- AC
- Protection Type
- overvoltage protection signalling circuit
- Net Weight
- 1.14 kg
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV EN/IEC 60947-5-1
- Supply Frequency
- 50/60 Hz
- Safety Level
- can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired EN/IEC 61508