Końcówka Serii
This pressure transmitter is part of the XMLP range, an offer of electronic pressure sensors. The XMLP transmitters are designed for the vacuum measuring and the pressure measuring. They are compatible with a large number of fluids. This product has a pressure range of 0bar to 16bar, with a maximum permissible accidental pressure at 48bar and a destruction pressure at 96bar. Made of stainless steel, this transmitter is compact and rugged. It has an analogue output (0V to 10V), wich delivers a signal proportional to the measured pressure. It is appropriate for controlling air, fresh water, hydraulic oil, gas and refrigeration fluid. This pressure transmitter features a compact metal body, a SAE 7/16-20UNF-2B (female with Schrader pin) 316L stainless steel fluid connector and a M12 electrical connector. It is suitable for machine tools, moulding presses, stamping presses and lifting gear. It complies with RCM, CULus, CE, EAC certifications, and with NSF ANSI 61 and EN/IEC 61326-2-3 standards. Dedicated accessories, to be ordered separatly, are available to facilitate the setting of the transmitter. Switches with a display, sealing gaskets, pre-wired connectors, etc. It operates in all positions. The transmitters of the XMLP range integrate a ceramic pressure measuring cell, providing a high level of sensitivity and good resistance to abrasive fluids.
Part Number
XMLP016BD790
Tariff Code
9026208000
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Poproś o wycenę, a prześlemy Ci informacje o dostępności i cenie.

Specifications

Pressure Sensor Type
pressure transmitter
Type Of Output Signal
analogue
Range Of Product
Telemecanique Pressure sensors XM
Electrical Connection
1 male connector M12 4 pins
Pressure Sensor Size
16-16 bar
Product Or Component Type
electronic pressure sensors
Type Of Packing
individual
Local Display
without
Pressure Sensor Name
XMLP
Current Consumption
< 7 mA
Fluid Connection Type
SAE 7/16-20UNF-2B (female) with schrader
Analogue Output Function
0...10 V, 3-wire
Controlled Fluid
fresh water 0-135 °C) || air -40-135 °C) || hydraulic oil -40-135 °C) || gas -40-135 °C) || refrigeration fluid -40-135 °C)
Quantity Per Set
set of 1
Electrical Circuit Type
control circuit
[Us] Rated Supply Voltage
24 V DC SELV 12-33 V)

Complementary

Accuracy
0.1 % of the measuring range
Diameter
26 mm
[Uimp] Rated Impulse Withstand Voltage
0.5 kV
Drift Of The Zero Point
+/- 0.02 % of measuring range/°K
Electromagnetic Compatibility
electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV || electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact || 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm || immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz || susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...3000 MHz || radiated RF fields EN/IEC 61000-4-6 10 V 0.01...80 MHz
Materials In Contact With Fluid
stainless steel type AISI 303
Length
44 mm
Net Weight
0.1 kg
Mechanical Durability
10000000 cycles
Operating Position
any position
Measurement Accuracy
+/- 0.5 % of the measuring range
Protection Type
reverse polarity || load short-circuit
Drift Of The Sensitivity
+/- 0.02 % of measuring range/°K
Maximum Permissible Accidental Pressure
48 bar
Destruction Pressure
96 bar
Response Time On Output
<= 2 ms 10...90 % of full scale
Pressure Setting Range
0-16 bar

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1511013EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
RCM || EAC || cULus || CE
Ambient Air Temperature For Operation
-30-85 °C
Standards
EN/IEC 61326-2-3 || NSF ANSI 61
Shock Resistance
100 gn 11 ms EN/IEC 60068-2-27
Vibration Resistance
20 gn 15-2000 Hz) EN/IEC 60068-2-6
Ip Degree Of Protection
IP65 conforming to EN/IEC 60529 || IP67 conforming to EN/IEC 60529 || IP69K conforming to EN/IEC 60529
Ambient Air Temperature For Storage
-50-100 °C
Protective Treatment
TC

Dokumenty

Data Sheet

Pobierz