- Contacts Usage
- standard
- Terminals Description Iso N°1
- (13-14)NO
- Short-Circuit Protection
- 10 A cartridge fuse gG EN/IEC 60947-5-1
- Operating Force
- 2.3 N NO changing electrical state
- Operating Travel
- 2.6 mm NO changing electrical state) || 4.3 mm total travel)
- Contacts Material
- silver alloy (Ag/Ni)
- Positive Opening
- without
- [Ith] Conventional Free Air Thermal Current
- 10 A EN/IEC 60947-5-1
- Net Weight
- 0.064 kg
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV EN 60947-1
- Cad Overall Height
- 47 mm
- Current Consumption
- 14 mA
- Device Presentation
- basic sub-assemblies
- Electrical Durability
- 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
- Service Life
- 100000 h at rated voltage and 25 °C
- Surge Withstand
- 1 kV IEC 61000-4-5
- [Ui] Rated Insulation Voltage
- 600 V 3)EN 60947-1
- Signalling Type
- steady
- Operating Torque
- 0.05 N.m NO changing electrical state
- [Ie] Rated Operational Current
- 3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 || 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1
- Supply Voltage Limits
- 195-264 V AC
- Mechanical Durability
- 5000000 cycles
- Electrical Reliability
- λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4 || λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4
- Tightening Torque
- 0.8-1.2 N.m EN 60947-1
- Cad Overall Width
- 30 mm
- Shape Of Screw Head
- cross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm