Wago

2004-1306

1 / 3
thumbnail
thumbnail
thumbnail
Part Number
2004-1306
Tariff Code
85369010000
UPC
4045454537487
ETIM
Group Code : EG000012
Group Description : Terminal blocks
Class Description : Feed-through terminal block
Class Code : EC000897
Version : 7
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Poproś o wycenę, a prześlemy Ci informacje o dostępności i cenie.

Ratings Per Iec/En

Ratings per
IEC/EN 60947-7-1
Nominal voltage (III/3)
800 V
Rated impulse voltage (III/3)
8 kV
Rated current
32 A
Current at conductor cross-section (max.) mm²
41 A
Legend (ratings)
(III / 3) ≙ Overvoltage category III / Pollution degree 3

Environmental Requirements

Processing temperature
-35 … +85 °C
Continuous operating temperature
-60 … +105 °C

Physical Data

Width
6.2 mm / 0.244 inches
Height
65.5 mm / 2.579 inches
Depth from upper-edge of DIN-rail
32.9 mm / 1.295 inches

Material Data

Note (material data)
<a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
Color
Yellow
Material group
I
Insulation material
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.150 MJ
Weight
8.370 g

Mechanical Data

Mounting type
DIN-35 rail
Marking level
Center/side marking

Specifications

Product Group Code
0022

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4045454537487
Customs tariff number
85369010000

Ex Information

Reference hazardous areas
See application instructions in section “Knowledge and Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 05 ATEX 1095 U / IECEx: PTB 05.0033U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550 V
Rated current (Ex e II)
30 A

Ratings Per Csa

Approvals per
CSA 22.2 No 158
Rated voltage CSA (Use Group B)
600 V
Rated current CSA (Use Group B)
30 A
Rated voltage CSA (Use Group C)
600 V
Rated current CSA (Use Group C)
30 A

Power Loss

Power loss, per pole (potential)
1.024 W
Rated current IN for specified power loss
32 A
Resistance value for specified, current-dependent power loss
0.001 Ω

Connection 1

Connection technology
Push-in CAGE CLAMP®
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
4 mm²
Solid conductor
0.5 … 6 mm² / 20 … 10 AWG
Solid conductor; push-in termination
1.5 … 6 mm² / 14 … 10 AWG
Fine-stranded conductor
0.5 … 6 mm² / 20 … 10 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 4 mm² / 20 … 12 AWG
Fine-stranded conductor; with ferrule; push-in termination
1.5 … 4 mm² / 18 … 12 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
Strip length
11 … 13 mm / 0.43 … 0.51 inches
Wiring direction
Front-entry wiring

Ratings Per Ul 1059

Approvals per
UL 1059
Rated voltage UL (Use Group B)
600 V
Rated current UL (Use Group B)
30 A
Rated voltage UL (Use Group C)
600 V
Rated current UL (Use Group C)
30 A