- Number of analog inputs
- 2
- Total number of channels (module)
- 2
- Signal type
- Current
- Signal type (current)
- 4 … 20 mADC
- Supply voltage (sensor)
- 16.5 VDC; Transmitter supply UV at 20 mA
- Sensor connection
- 2 x (2-wire)
- Input filter
- Parameterizable
- Input filter: parametrizable (channel by channel)
- Yes
- Signal characteristics
- Single-ended
- Diagnostics
- Wire break, measurement range overflow
- Resolution [bit]
- 12 bits
- Power consumption Pmax.
- 1.60 W (with slaves (20 mA))
- Data width
- 2 x 2-byte data; 2 x 2-byte data + 2n x 4-byte data (n = number of dynamic variables); 2 x 2-byte data + 6-byte mailbox
- Overvoltage protection
- 30 V, reverse polarity protected
- Conversion time (typ.)
- 10 ms
- Measurement error (reference temperature)
- 25 °C
- Measurement error, deviation (max.) from the upper-range value
- 0.2 %
- Temperature error (max.) of the upper-range value
- 0.01 %/K
- Intrinsic safety Ex i
- Yes
- Supply voltage (system)
- 5 VDC; via data contacts
- Current consumption (5 V system supply)
- 25 mA
- Supply voltage (field)
- 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Current consumption, field supply (module with no external load)
- 26 mA
- HART devices per channel
- 1 device (single-drop, no multi-drop)
- HART modems per channel
- 1 modem (no multiplex)
- Power loss Pl
- 0.62 W (without slaves)
- Isolation
- 300 VAC system/field
- Indicators
- LED (A, E) green: Function HART 1, HART 2; LED (B, F) red: Error HART 1, HART 2
- Number of incoming power jumper contacts
- 2
- Number of outgoing power jumper contacts
- 2
- Current carrying capacity (power jumper contacts)
- 1 A
- Marking
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I