Wago

753-492

2-channel analog input; 4 … 20 mA; Differential input
753-492
753-492
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
£426.80
1
Metody płatności:
Łącznie 53 części w magazynie od 10 dostawców

Additional Information

Part Number
753-492
UPC
4050821867500
Tariff Code
85389099990
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - analogue I/O module
Class Code : EC001596
Version : 7

Environmental Requirements

Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 … 2000 m / 0 … 6562 ft
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Vibration resistance
Per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
Per EN 61000-6-2
EMC emission of interference
Per EN 61000-6-4
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: inputs/outputs
8 x CAGE CLAMP®
Connection type 1
Inputs/outputs
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Strip length
9 … 10 mm / 0.35 … 0.39 inches

Physical Data

Width
12 mm / 0.472 inches
Height
100 mm / 3.937 inches
Depth
69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail
62.6 mm / 2.465 inches

Material Data

Color
Light gray
Housing material
Polycarbonate; polyamide 6.6
Fire load
0.882 MJ
Weight
56.500 g
Conformity marking
CE

Technical Data

Number of analog inputs
2
Total number of channels (module)
2
Signal type
Current
Signal type (current)
4 … 20 mADC
Sensor connection
2 x (2-wire)
Input filter
Low pass (1st order), fG = 5 kHz
Signal characteristics
Differential
Resolution [bit]
13 bits
Operating mode
Continuously sampling (default)
Input resistance (max.)
270 Ω
Data width
2 x 16-bit data; 2 x 8-bit control/status (optional)
Protection
Non-linear limiting
Admissible continuous overload
30 V
Crosstalk attenuation
80 dB
Monotonicity without error code
Yes
Measurement error (reference temperature)
25 °C
Measurement error, deviation (max.) from the upper-range value
0.05 %
Measurement error over entire temperature range
≤ 0.4 %
Temperature error (max.) of the upper-range value
0.01 %/K
Sampling duration
5 µs
Sampling delay (channel/channel)
1 µs
Sampling delay (module)
1 ms
Sampling repetition time
1 ms
Measurement range overflow/underflow
Status byte and LED
Measured value acquisition
Time synchronous within the module
Value of the least significant bit (LSB)
2.4 µA
Conversion method
SAR (Successive Approximation Register)
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
80 mA
Isolation
500 V system/field or channel/channel
Indicators
LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2

Mechanical Data

Mounting type
DIN-35 rail
Pluggable connector
Pluggable

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4050821867500
Customs tariff number
85389099990

Notes

Note
Pluggable connectors and coding fingers (753 Series) are not included.

Powiązane produkty