Wago
787-732
EPSITRON® ECO power supply; single-phase; output voltage 24 VDC; 10 A
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
€146.37
1
Metody płatności:
Łącznie 77 części w magazynie od 20 dostawców
Stan produktu:
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€69.84
Additional Information
- Part Number
- 787-732
- UPC
- 4045454908140
- Tariff Code
- 85044082900
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : DC-power supply
- Class Code : EC002540
- Version : 7
Safety And Protection
- Isolation voltage (pri.-sec.)
- DC 4.242 kV
- Isolation voltage (pri.-PE)
- DC 2.2 kV
- Isolation voltage (sec.-PE)
- DC 0.7 kV
- Protection class
- I
- Protection type
- IP20; per EN 60529
- Resistance to reverse feed
- ≤ DC 28 V
- Overvoltage category
- II
- Pollution degree
- 2
- Transient suppression (primary)
- Varistor
- Short-circuit-protected
- Yes
- Open-circuit-proof
- Yes
- Parallel operation
- Yes
- Series operation
- Yes
- MTBF
- 480,000 h (per IEC 61709)
Environmental Requirements
- Ambient temperature (operation)
- -10 … +70 °C
- Ambient temperature (storage)
- -25 … +85 °C
- Relative humidity
- ≤ 95% (no condensation permissible)
- Derating
- -2.33 %/K (> 40 °C; 230 VAC)
Connection Data
- Connection type 1
- Input/output
- Connection technology
- CAGE CLAMP®
- WAGO connector
- WAGO 745 Series
- Solid conductor
- 0.08 … 4 mm² / 28 … 12 AWG
- Fine-stranded conductor
- 0.08 … 4 mm² / 28 … 12 AWG
- Strip length
- 8 … 9 mm / 0.31 … 0.35 inches
- Note (conductor cross-section)
- 12 AWG: THHN, THWN
Signaling And Communication
- Signaling
- 1 x LED DC OK (green) || 1 x Overload LED (red)
- Operation status indicator
- Green LED (24 VDC OK) || Red LED (overload)
Physical Data
- Width
- 110 mm / 4.331 inches
- Height
- 92 mm / 3.622 inches
- Depth from upper-edge of DIN-rail
- 136 mm / 5.354 inches
Material Data
- Fire load
- 10.100 MJ
- Weight
- 1200.000 g
Input
- Phases
- 1
- Nominal input voltage Ui nom
- 1 x AC 100 … 240 V
- Input voltage range
- 1 x AC 90 … 264 V; DC 90 … 373 V
- Nominal mains frequency range
- 47 … 63 Hz; 0 Hz
- Input current Ii
- ≤ 1.5 A (230 VAC); ≤ 3 A (115 VAC)
- Discharge current
- ≤ 3.5 mA
- Inrush current
- ≤ 30 A
- Power factor
- ≥ 0.94 (230 VAC); ≥ 0.98 (115 VAC)
- Power factor correction (PFC)
- Active
- Mains failure hold-up time
- ≥ 20 ms (230 VAC)
Output
- Nominal output voltage Uo nom
- DC 24 V (SELV)
- Output voltage range
- DC 22 … 28 V (adjustable)
- Default setting
- DC 24 V
- Nominal output current Io nom
- 10 A (24 VDC)
- Nominal output power
- 240 W
- Deviation
- ≤ 1 %
- Residual ripple
- ≤ 100 mV (peak-to-peak)
- Overload behavior
- Constant power (in overload range: 1.15 … 1.4 x Io nom); Shutdown and automatic restart in the event of a short circuit
Standards And Specifications
- Conformity marking
- CE
- Standards/specifications
- EN 62368-1 || EN 61204-3 || CURus 60950-1 || CULus 508 || ANSI/ISA 12.12.01 (Class I Div. 2) || ATEX || IEC Ex || SEMI F47
Mechanical Data
- Mounting type
- DIN-35 rail
Specifications
- Product Group Code
- 0006
Commercial Data
- Packaging type
- Box
- Country of origin
- CN
- GTIN
- 4045454908140
- Customs tariff number
- 85044083900
Efficiency/Power Losses
- Power loss Pl
- ≤ 37.5 W (230 VAC; nominal load)
- Power loss (max.) Pl (max.)
- 53 W (110 VAC / 24 VDC; 11 A)
- Efficiency (typ.)
- 86 % (230 VAC)
<B>Circuit Protection</B>
- Internal fuse
- F 5 A / 250 VAC
- Backup fusing (required)
- An external DC fuse is required for the DC input voltage.
- Backup fusing (recommended)
- Circuit breaker: 10 A, 16 A; Tripping characteristic: B or C