Additional Information

Part Number
460

Specifications

Input Voltage (V)
190 to 480VAC
Maximum Input Power
6W
Input AC Line Frequency (Hz)
50/60Hz (50Hz will increase all delay timers by 20%.)
Output Form
Form C
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC B300; General Purpose: 10A @ 240VAC
Restart Delay Range
1 - 500s adjustable
Trip Delay Range
Over Under and Unbalanced Voltage: 1 - 30s adjustable; Single-Phase Faults (>25%UB): 1s fixed
Trip Point Accuracy (%)
±1%
Overvoltage Trip Voltage (%)
110%
Overvoltage Reset Voltage (%)
107%
Undervoltage Trip Voltage
90%
Undervoltage Reset Voltage (%)
93%
Voltage Unbalance Trip Point (%)
2 - 8% adjustable
Voltage Unbalance Reset (%)
Trip setting minus 1% (5-8%); Trip setting minute 0.5% (2-4%)
Protection Class
IP20 NEMA 1 (finger safe)
Termination Type
Torque: 6in-lbs; Wire: Stranded or solid 12 - 20AWG one per terminal
Mounting Method
35mm DIN rail or Surface Mount (#6 or #8 screws)
Operating Temperature
-40° to 70°C (-40° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Humidity
10-95% non condensing per IEC 68-2-3
Dimensions
3.50 in H x 2.08 in W x 2.35 in D (88.9 x 52.9 x 59.7 mm)
Weight (lbs/g)
0.7 lb. (11.2 oz. 317.5 g)

Documents

Data Sheet