1 / 1
thumbnail

Beschreibung

Aktiv Reif
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 800A 450kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 324mm x 210mm x 248mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
Part Number
LC1G800LSEA
Tariff Code
8536490065
EAN
39121529
UNSPSC
39121529
Zahlungsmethoden:
Bestes Angebot von:
FRVertrauenswürdiger Automa.Net Lieferant
Verfügbarkeit:
2 Stk.
Auf Lager
Aktualisiert am: 08-11-2024
Garantie:
12 Monate
Geschätzte Lieferung:
Auf Anfrage
Zustand:
Neuer Überschuss
Neuer Überschuss - Ein neuer, unbenutzter, unbeschädigter Artikel ohne Herstellergarantie. Der Artikel kann ohne Originalverpackung oder in Ersatzverpackung geliefert werden. Wenn vorhanden, könnte die Verpackung geöffnet worden sein.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen

Complementary

Product Certifications
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Height
388.5 mm
Power Dissipation Per Pole
70 W AC-1 - Ith 1050 A || 42 W AC-3 - Ith 800 A
Average Impedance
0.000065 Ohm
Auxiliary Contact Composition
1 NO + 1 NC
Connection Pitch
70 mm
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1
Mounting Support
plate
Hold-In Power Consumption In W
11.0-11.0 W
Rated Breaking Capacity
5870 A at 440 V
Associated Fuse Rating
800 A aM at <= 440 V for motor || 630 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
Net Weight
17.3 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV
Inrush Power In Va
670-670 VA
Pole Contact Composition
3 NO
Connections - Terminals
power circuit: bar 2 - busbar cross section: 52 x 20 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 0.75-2.5 mm² - cable stiffness: flexible with cable end
Coil Technology
built-in bidirectional peak limiting
Operating Time
40...70 ms closing || 15...50 ms opening
Maximum Operating Rate
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Mechanical Durability
5 Mcycles
Tightening Torque
58 N.m
Compatibility Code
LC1G
Hold-In Power Consumption In Va
17.0-17.0 VA
Width
211 mm
Overvoltage Category
III
Depth
266 mm
Maximum Horse Power Rating
300 hp at 200/208 V 60 Hz || 350 hp at 230/240 V 60 Hz || 700 hp at 460/480 V 60 Hz || 800 hp at 575/600 V 60 Hz
Motor Power Kw
200 kW at 230 V AC 50/60 Hz (AC-3e) || 335 kW at 400 V AC 50/60 Hz (AC-3e) || 355 kW at 415 V AC 50/60 Hz (AC-3e) || 375 kW at 440 V AC 50/60 Hz (AC-3e) || 425 kW at 500 V AC 50/60 Hz (AC-3e) || 560 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V AC 50/60 Hz (AC-3e) || 250 kW at 230 V AC 50/60 Hz (AC-3) || 450 kW at 400 V AC 50/60 Hz (AC-3) || 450 kW at 415 V AC 50/60 Hz (AC-3) || 450 kW at 440 V AC 50/60 Hz (AC-3) || 500 kW at 500 V AC 50/60 Hz (AC-3) || 560 kW at 690 V AC 50/60 Hz (AC-3) || 450 kW at 1000 V AC 50/60 Hz (AC-3) || 200 kW at 230 V AC 50/60 Hz (AC-4) || 375 kW at 400 V AC 50/60 Hz (AC-4) || 355 kW at 415 V AC 50/60 Hz (AC-4) || 375 kW at 440 V AC 50/60 Hz (AC-4) || 400 kW at 500 V AC 50/60 Hz (AC-4) || 475 kW at 690 V AC 50/60 Hz (AC-4) || 400 kW at 1000 V AC 50/60 Hz (AC-4)
[Ui] Rated Insulation Voltage
1000 V
Inrush Power In W
390 W
[Icw] Rated Short-Time Withstand Current
5.5 kA - 10 s || 4.6 kA - 30 s || 3.6 kA - 1 min || 2.6 kA - 3 min || 1.7 kA - 10 min

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2105013
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI2105013
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Environment

Ambient Air Temperature For Operation
-25-60 °C
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Mechanical Robustness
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Color
dark grey
Permissible Ambient Air Temperature Around The Device
-40-70 °C at Uc

Specifications

[Uc] Control Circuit Voltage
200...500 V AC 50/60 Hz || 200...500 V DC
[Ue] Rated Operational Voltage
<= 1000 V AC 50/60 Hz || <= 460 V DC
Range Of Product
TeSys Giga
Control Circuit Voltage Limits
operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Contactor Application
power switching || motor control
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
[Ie] Rated Operational Current
1050 A (at <40 °C) at <= 1000 V AC-1 || 800 A (at <60 °C) at <= 440 V AC-3
Poles Description
3P
Device Short Name
LC1G

Dokumente

Data Sheet

Herunterladen

CAD Models

traceparts
traceparts
Herunterladen