RXM miniature relays are part of Harmony Electromechanical Relays. This is a plug in relay to be mounted on a RXZE socket. It is a 2 C/O relay with current rating of 5A, control circuit voltage of 120 V AC 50/60 Hz. It also offers a mechanical indicator where an orange flag indicates the relay contact status. The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts. Workablity for hard-wired logic automated systems to complement the functions of industrial progammable logic controllers (PLCs). Its design is fit for industrial machines, packaging, textile, HVAC, automation control panels, low/medium voltage switchgear, motor controls, PLC Interfaces, power supplies, building or medical equipment, lighting controls. It is a green premium product and conforms to international standard and certifications like IEC, CE. RXM relay need to be used with a RXZE socket RXZE1M2C. To protect against vibrations, metal clamp RXZ410/RXZ420 can be added to the socket. It is sold in lots of 10 and reference includes relay only. The RXMLB plug-in relays are a series of industrial plug-in relays designed for both simple and complex automation systems and available with 2 CO (5A), 4 CO (3A) contacts.- Part Number
- RXM2LB1F7
- Tariff Code
- 8536490075
- EAN
- 39122324
- UNSPSC
- 39122324
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Environment
- Standards
- CE || IEC 61810-1 (iss. 2)
- Pollution Degree
- 3
- Ambient Air Temperature For Operation
- -40-55 °C
- Vibration Resistance
- 3 gn +/- 1 mm 10-50 Hz)operating IEC 60068-2-6 || 6 gn +/- 1 mm 10-50 Hz)not operating IEC 60068-2-6
- Shock Resistance
- 30 gnnot operating IEC 60068-2-27 || 10 gnin operation IEC 60068-2-27
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Ambient Air Temperature For Storage
- -40-85 °C
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2108011EN
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI2108011EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Maximum Switching Capacity
- 1250 VA AC || 140 W DC
- Safety Reliability Data
- B10d = 100000
- [Uc] Control Circuit Voltage
- 120 V AC 50/60 Hz
- Operating Rate
- <= 1200 cycles/hour under load || <= 18000 cycles/hour no-load
- Protection Category
- RT I
- Test Levels
- level A group mounting
- Contacts Material
- silver alloy (Ag/Ni)
- Dielectric Strength
- 2000 V AC between coil and contact with basic insulation || 2000 V AC between poles with basic insulation || 1000 V AC between contacts with micro disconnection
- Status Led
- without
- Net Weight
- 0.031 kg
- Cad Overall Height
- 27 mm
- Maximum Switching Voltage
- 250 V AC || 28 V DC
- Control Type
- without push-button
- Average Resistance
- 4430 Ohm at 23 °C +/- 10 %
- Minimum Switching Capacity
- 170 mW
- Rated Operational Voltage Limits
- 96...132 V AC
- Contacts Type And Composition
- 2 C/O
- [Ie] Rated Operational Current
- 5 A AC-1/DC-1) NO IEC || 2.5 A AC-1/DC-1) NC IEC || 1 A 28 V DC-13) NO
- [Ui] Rated Insulation Voltage
- 250 V IEC
- Contact Operation
- standard
- Minimum Switching Current
- 10 mA
- Electrical Durability
- 100000 cycles for resistive load || 50000 cycles, 1 A at 28 V, DC-13 NO
- Mechanical Durability
- 10000000 cycles
- Operating Position
- any position
- Operating Time
- 20 ms between coil de-energisation and making of the Off-delay contact || 20 ms between coil energisation and making of the On-delay contact
- Load Current
- 5 A 250 V AC || 5 A 28 V DC
- Drop-Out Voltage Threshold
- >= 0.15 Uc AC
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV 1.2/50 µs IEC 61810-7
- Cad Overall Width
- 21 mm
- Minimum Switching Voltage
- 17 V
- Cad Overall Depth
- 46 mm
- Average Coil Consumption In Va
- 1.2-1.2 AC
- [Ithe] Conventional Enclosed Thermal Current
- 5 A -40-55 °C
Specifications
- Utilisation Coefficient
- 20 %
- Range Of Product
- Harmony Electromechanical Relays
- Product Or Component Type
- plug-in relay
- Series Name
- Miniature
- Coil Interference Suppression
- without
- Sale Per Indivisible Quantity
- 10
- Device Short Name
- RXM
Dokumenty
Data Sheet
PobierzModele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne