- AC failure bridging time @ I
- > 20 ms @ 230 V AC / > 20 ms @ 115 V AC
- Conformal coating
- No
- Degree of efficiency
- 93%
- Derating
- > 60°C (2.5% / 1°C)
- Earth leakage current, max.
- 3.5 mA
- Housing version
- Metal, corrosion resistant
- MTBF
- > 1.000.000 h according IEC 1709 (SN29500)
- Mounting position, installation notice
- Horizontal on DIN rail TS 35, top and bottom 50 mm clearance for free air flow, 10 mm clearance to neighbouring active subassemblies with full load, 5 mm with passive neighbouring subassemblies, direct row mounting with 90% rated load
- Operating temperature
- -25 °C...70 °C
- Power factor (approx.)
- > 0.9
- Power loss, idling
- 10 W
- Power loss, nominal load
- 36.1 W
- Protection degree
- IP20
- Series switching capability
- Yes
- Short-circuit protection
- Yes, internal
- Start-up
- ≥ -40 °C
- Surge voltage category
- III