Weidmuller

0324120000

SAKC 10 2STB
0324120000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
€12.23

Additional Information

Part Number
0324120000

Approvals

Approvals
CE, CSA, EAC, MARITREG, UR
ROHS
Conform
UL File Number Search
E60693

Dimensions And Weights

Width
12 mm
Width (inches)
0.472 inch
Height
65 mm
Height (inches)
2.559 inch
Depth
52.5 mm
Depth (inches)
2.067 inch
Net weight
46.2 g

Csa Rating Data

Certificate No. (CSA)
12400-186
Current size C (CSA)
25 A
Current size D (CSA)
5 A
Voltage size C (CSA)
600 V
Voltage size D (CSA)
600 V
Wire cross section max. (CSA)
10 AWG
Wire cross section min. (CSA)
20 AWG

Additional Technical Data

Explosion-tested version
No
Installation advice
Rail
Open sides
right
Type of mounting
Snap-on

Material Data

Material
KrG
Colour
medium yellow
UL 94 flammability rating
V-0, 5VA

Safety Note

Safety notice
Safety Information

Classifications

ETIM 6.0
EC000902
ETIM 7.0
EC000902
EClass 9.0
27-14-11-26
EClass 9.1
27-14-11-26
EClass 10.0
27-14-11-26
UNSPSC
30-21-18-11

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

System Specifications

Version
Screw connection, Spacer, With sockets, One end without connector
End cover plate required
Yes
Number of potentials
1
Number of levels
1
Number of clamping points per level
2
Number of potentials per tier
1
Levels cross-connected internally
No
PE connection
No
Rail
TS 32
N-function
No
PE function
No
PEN function
No

Disconnect Terminals

Cross-disconnect
without
Integral test socket
Yes
Slitting
pluggable

Temperatures

Storage temperature, max.
40 °C
Storage temperature, min.
10 °C
Storage temperature
10 °C...40 °C
Continuous operating temp., min.
-60 °C
Continuous operating temp., max.
130 °C

Rating Data

Rated cross-section
10 mm²
Rated voltage
500 V
Rated current
26 A
Current at maximum wires
27 A
Standards
IEC 60947-7-1
Volume resistance according to IEC 60947-7-x
0.56 mΩ
Power loss in accordance with IEC 60947-7-x
1.82 W
Rated impulse withstand voltage
6 kV
Pollution severity
3

Conductors For Clamping (Rated Connection)

Blade size
1.0 x 5.5 mm
Clamping range, max.
10 mm²
Clamping range, min.
0.33 mm²
Clamping screw
M 4
Connection cross-section, stranded, max.
10 mm²
Connection cross-section, stranded, min.
1.5 mm²
Connection direction
on side
Gauge to IEC 60947-1
B6
Number of connections
2
Stripping length
12 mm
Tightening torque, max.
2.4 Nm
Tightening torque, min.
1.2 Nm
Torque level with DMS electric screwdriver
4
Type of connection
Screw connection
Wire connection cross section AWG, max.
AWG 8
Wire connection cross section AWG, min.
AWG 22
Wire connection cross section, finely stranded, max.
10 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max.
10 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min.
0.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
10 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
10 mm²
Wire connection cross-section, finely stranded, min.
0.5 mm²
Wire connection cross-section, solid core, max.
10 mm²
Wire connection cross-section, solid core, min.
0.5 mm²

Ul Rating Data

Certificate No. (UR)
E60693
Conductor size Factory wiring max. (UR)
8 AWG
Conductor size Factory wiring min. (UR)
26 AWG
Conductor size Field wiring max. (UR)
8 AWG
Conductor size Field wiring min. (UR)
22 AWG
Current size C (UR)
25 A
Voltage size C (UR)
600 V