Weidmuller

2619120000

VPU AC I 1 R 440/25 LCF
2619120000
2619120000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
€104.24

Additional Information

Part Number
2619120000

General Data

Altitude
≤ 2000 m
Colour
black
Design
Installation housing; 2TE, Insta IP 20
Optical function display
green = OK; red = arrester is defective - replace
Protection degree
IP20 in installed state
Rail
TS 35
Segment
Power distribution
Suitable for
Count-in installation (leakage current free)
UL 94 flammability rating
V-0
Version
Surge protection, with remote contact

Approvals

Approvals
CE
ROHS
Conform

Insulation Coordination Acc. To En 50178

Pollution severity
2
Surge voltage category
III

Rated Data Iec / En

Discharge current I
25 kA
Energy coordination (≤10 m)
Type I, Type II, Type III
Follow-on current extinguishing capability I
Not available due for technical reasons
Frequency range, max.
60 Hz
Frequency range, min.
50 Hz
Fuse
250 A gL (if back up fuse > 250 A)
Leakage current at U
5 µA
Lightning test current I
25 kA
Low voltage network
Single-phase, TN, TN-S
Max. continuous voltage, Uc (AC)
440 V
Number of poles
1
Protection level U
≤ 2.5 kV
Rated load current I
100 A
Rated voltage (AC)
400 V
Requirements category acc. to IEC 61643-11
Type I, Type II
Requirements class, acc. to EN 61643-11
T1, T2
Response time
≤ 25 ns
Short-circuit current rating I
50 kA
Signalling contact
250 V 1A 1CO
Standards
IEC61643-11, EN61643-11, EN 60068-2-27:2009, EN 60068-2-64:2008, EN 60068-2-6:2008
Suitable for
Count-in installation (leakage current free)
Temporary surge voltage (over-voltage) - TOV
762 V
Voltage type
AC

Dimensions And Weights

Width
36 mm
Width (inches)
1.417 inch
Height
106 mm
Height (inches)
4.173 inch
Depth
93 mm
Depth (inches)
3.661 inch
Net weight
25 g

Connection Data

Wire connection method
Screw connection
Type of connection
Screw connection
Stripping length, rated connection
13 mm
Tightening torque, min.
2 Nm
Tightening torque, max.
3 Nm
Clamping range, rated connection
16 mm²
Clamping range, min.
6 mm²
Clamping range, max.
35 mm²
Wire cross-section, solid, min.
6 mm²
Wire cross-section, solid, max.
35 mm²
Wire connection cross-section, finely stranded, min.
6 mm²
Wire connection cross section, finely stranded, max.
35 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min.
6 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max.
35 mm²
Connection cross-section, stranded, min.
6 mm²
Connection cross-section, stranded, max.
35 mm²

Classifications

ETIM 6.0
EC000941
ETIM 7.0
EC000941
EClass 9.0
27-13-08-05
EClass 9.1
27-13-08-05
EClass 10.0
27-13-08-05
UNSPSC
30-21-19-22

Connection Data, Remote Alert

Connection type
Screw connection, pluggable
Stripping length
8 mm
Cross-section for connected wire, solid core, min.
0.14 mm²
Cross-section for connected wire, solid core, max.
1.5 mm²

Temperatures

Humidity
5 - 95% rel. humidity
Operating temperature, max.
85 °C
Operating temperature, min.
-40 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-40 °C...85 °C
Storage temperature
-40 °C...85 °C