This product is part of the Modicon X80 range, a common platform of modules for Modicon M580 and M340 Programmable Automation Controllers (PAC). This PTO module has 2 channels, 4 inputs with sink (positive) discrete logic. It is a PTO module with an input/output voltage 24V DC, an output current of 50mA and a maximum current consumption of 200mA at 3.3V DC. This product is robust, high quality and based on the latest innovative technology. It is furnished with two 28-way connectors for electrical connection. There is no insulation between channels. It is suitable for medium to large process applications. It meets EN 61131-2, EN 61000-6-4, EN 61000-6-2 and EN 61010-2-201 standards. This output compatible with signal converter (USIC), RS422, 7mA input and source input, 5V to 24V. Input compatible with 2-wire/3-wire proximity sensor 19.2V to 30V conforming to IEC 947-5-2. Modicon X80 consists in a compatible modules common platform that reduce maintenance and training costs with same spare parts in stock, and unique training for different Programmable Automation Controllers (PAC).- Country of Origin
- FR
- Part Number
- BMXMSP0200
- Tariff Code
- 85389099
- EAN
- 3595863998634
- UNSPSC
- 26101205
Zahlungsmethoden:
- Bestes Angebot von:
- Vertrauenswürdiger Automa.Net Lieferant
- Verfügbarkeit:
- 2 Stk.Auf LagerAktualisiert am: 07-11-2024
- Garantie:
- 12 Monate
- Geschätzte Lieferung:
- Auf Anfrage
- Zustand:
- Neu versiegelt ab Werk
Neu versiegelt ab Werk - Ein brandneuer, unbenutzter, ungeöffneter, unbeschädigter Artikel in seiner original vom Hersteller versiegelten Verpackung.
Insgesamt 33 Parts In-Stock von 10 Distributors
Versandinformationen
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen
Verfügbare Angebote (9)
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
€418.59
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 61131-2 || EN/IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201 || IACS E10 || EN/IEC 61000-6-5, interface type 1 and type 2 || EN/IEC 61850-3, location G || EN/IEC 60079-0
- Environmental Characteristic
- hazardous location class I division 2
- Directives
- 2014/35/EU - low voltage directive || 2014/30/EU - electromagnetic compatibility || 2014/34/EU - ATEX directive
- Derating Factor
- without
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Electrical Connection
- 2 connectors 28 pins
- Current Per Channel
- 0.4 A
- Number Of Outputs
- 1 pulse output || 2 auxiliary output
- Insulation Resistance
- > 10 MOhm
- Product Certifications
- CE || UL || CSA || RCM || EAC || Merchant Navy || ATEX zone 2/22 || IECEx zone 2/22
- Response Time
- < 200 µs for position completed input and drive ready input || < 60 µs for origin input and proximity input
- Current Consumption
- 35 mA 24 V DC preactuator || 150 mA 3.3 V DC typical || 200 mA 3.3 V DC maximum
- Discrete Output Current
- 50 mA
- Current State 0 Guaranteed
- <= 1.5 mA
- Voltage State 0 Guaranteed
- 5 V
- Load Impedance Ohmic
- 15000 Ohm
- Input Current
- 4.3 mA
- Current State 1 Guaranteed
- >= 2 mA
- Operating Threshold
- > 12 V no error supply voltage || > 8 V error supply voltage
- Output Short-Circuit Protection
- by current limiter and electronic circuit breaker
- Output Voltage Limits
- 19...30 V
- Insulation Between Channels
- no insulated
- Input Voltage
- 24 V DC
- Insul Btwn Prim And Second
- 1500 Vrms
- Local Signalling
- for module operating (RUN) 1 LED (green) || for external fault (I/O) 1 LED (red) || for internal fault, module failure (ERR) 1 LED (red) || for download (DL) 1 LED (green) || for channel status (CH00) 8 LEDs (green) || for channel status (CH01) 8 LEDs (green)
- Output Overload Protection
- by current limiter and electronic circuit breaker
- Output Voltage
- 24 V DC
- Module Format
- standard
- Reverse Polarity Protection
- by reverse mounting diode on output || integrated on input
- [Ures] Residual Voltage
- 0.15 V at state 1
- Maximum Leakage Current
- 0.05 mA at state 0
- Preactuator Voltage Detection Threshold
- < 8 V error preactuator voltage auxiliary output || < 8 V no error preactuator voltage auxiliary output || > 14 V error preactuator voltage pulse output || > 14 V no error preactuator voltage pulse output
- Response Time On Output
- 1.2...1.5 ms on appearance || 1.2...1.5 ms on disappearance
- Voltage State 1 Guaranteed
- >= 11 V
Specifications
- Range Of Product
- Modicon X80
- Number Of Inputs
- 4
- Output Compatibility
- signal converter (USIC) || RS422, 7 mA input || source input, 5 V to 24 V
- Product Or Component Type
- PTO module
- Output Frequency
- 200 kHz <0.5 m with USIC and VW3M8210R05 || 100 kHz <5 m with the normal source input circuit || 200 kHz <10 m with the RS422 compatible circuits
- Input Compatibility
- 2-wire/3-wire proximity sensor 19.2-30 V IEC 947-5-2
- Number Of Channels
- 2
- Discrete Input Type
- current sink yes origin input IEC 61131-2 type 3 || current sink yes proximity input and limit switch input IEC 61131-2 type 3 || current sink or source counter in position input IEC 61131-2 type 3 || current sink or source drive ready, emergency input IEC 61131-2 type 3