Schneider Electric
JGL34250WU31X
Circuit breaker, PowerPacT J, 250A, 3 pole, 480VAC, 35kA, lugs, Micrologic 3.2, 80%, mission critical
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
Preisanfrage senden
1
Zahlungsmöglichkeiten:
Produktbedingungen:
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
Preisanfrage senden
Additional Information
- Part Number
- JGL34250WU31X
- UPC
- 785901949114
- UNSPSC
- 39121601
- Tariff Code
- 8536200020
- Country of Origin
- US
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact J
- Range
- PowerPact
- Device Application
- distribution
Environment
- Ambient Air Temperature For Operation
- -2-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- front cover IP40
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Complementary
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL250JD
- [Ics] Rated Service Breaking Capacity
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology
- electronic, standard, MicroLogic 3.2, LI
- Trip Unit Name
- MicroLogic 3.2
- Height
- 191 mm
- [Ue] Rated Operational Voltage
- 480/277 V AC 50/60 Hz IEC 60947-3
- Tightening Torque
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mounting Support
- lug
- Breaking Capacity Code
- G
- Local Signalling
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- lugs, line || lugs, load
- Net Weight
- 2.4 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 25 mm
- Line Rated Current
- 250-250 A
- Utilisation Category
- category A
- Long Time Pick-Up Adjustment Range
- 0.25...1 x In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Communication Interface
- Modbus || Ethernet
- Poles Description
- 3P
- Protection Type
- overload protection || short-circuit protection
- Awg Gauge
- AWG 3/0...350 kcmil aluminium/copper terminals
- Width
- 104 mm
- Depth
- 86 mm
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206032EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206032EN
- Eu Rohs Directive
- Compliant with Exemptions