Schneider Electric
JGL34250WU31X
1 / 1
Descrizione
Attivo maturo
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides Micrologic Standard with a 3.2 trip unit and an LI function with a breaking capacity of 35kA at 480VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 250A, 3 pole, circuit breaker has a breaking capacity of 35kA at 480VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.- Country of Origin
- US
- Part Number
- JGL34250WU31X
- Tariff Code
- 85362090
- EAN
- 785901949114
- UPC
- 785901949114
- UNSPSC
- 39121601
Metodi di pagamento:
- Migliore offerta da:
- Fornitore Automa.Net di fiducia
- Disponibilità:
- 10 pz.DisponibileAggiornato il: 08-11-2024
- Garanzia:
- 12 mesi
- Consegna stimata:
- Su richiesta
- Condizione:
- Nuovo sigillato in fabbrica
Nuovo sigillato in fabbrica - Un articolo nuovo di zecca, inutilizzato, non aperto, non danneggiato, nella sua confezione originale sigillata dal produttore.
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact J
- Range
- PowerPact
- Device Application
- distribution
Environment
- Ambient Air Temperature For Operation
- -2-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- front cover IP40
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Complementary
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL250JD
- [Ics] Rated Service Breaking Capacity
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology
- electronic, standard, MicroLogic 3.2, LI
- Trip Unit Name
- MicroLogic 3.2
- Height
- 191 mm
- [Ue] Rated Operational Voltage
- 480/277 V AC 50/60 Hz IEC 60947-3
- Tightening Torque
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mounting Support
- lug
- Breaking Capacity Code
- G
- Local Signalling
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm 1 LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- lugs, line || lugs, load
- Net Weight
- 2.4 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 25 mm
- Line Rated Current
- 250-250 A
- Utilisation Category
- category A
- Long Time Pick-Up Adjustment Range
- 0.25...1 x In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Communication Interface
- Modbus || Ethernet
- Poles Description
- 3P
- Protection Type
- overload protection || short-circuit protection
- Awg Gauge
- AWG 3/0...350 kcmil aluminium/copper terminals
- Width
- 104 mm
- Depth
- 86 mm
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206032EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206032EN
- Eu Rohs Directive
- Compliant with Exemptions