ABB

AF26N1-30-00-14

AF26N1-30-00-14 250-500V50/60HZ-DC Contactor
AF26N1-30-00-14
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Additional Information

Part Number
AF26N1-30-00-14
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, AC switching
Class Code : EC000066
Version : 7

Dimensions

Product Net Width
45 mm
Product Net Depth / Length
86 mm
Product Net Height
86 mm
Product Net Weight
0.35 kg

Technical

Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 1.5 ... 10 mm²Flexible with Insulated Ferrule 1x 1.5 ... 10 mm²Flexible with Insulated Ferrule 2x 1.5 ... 4 mm²Rigid Solid 1/2x 2.5 ... 4 mm²Rigid Stranded 1/2x 2.5 ... 10 mm²
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Minimum Mounting Distance
Other Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 0 mm
Mounted Auxiliary Contacts
0 NO, 0 NC
Mounting Position
1, 1 +/-30°, 2, 3, 4, 5
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Main Contacts NC
0
Number of Main Contacts NO
3
Number of Poles
3
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms
Pollution Degree
3
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.8 Wat Rated Operating Conditions AC-3 per Pole 0.6 W
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V60 Hz 250 ... 500 VDC Operation 250 ... 500 V
Rated Frequency (f)
Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 Vacc. to UL/CSA 600 V
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 45 A(690 V) 60 °C 40 A(690 V) 70 °C 32 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 26 A(440 V) 60 °C 26 A(500 V) 60 °C 23 A(690 V) 60 °C 17 A(380 / 400 V) 60 °C 26 A(220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 26 A(440 V) 60 °C 26 A(500 V) 60 °C 23 A(690 V) 60 °C 17 A(380 / 400 V) 60 °C 26 A(220 / 230 / 240 V) 60 °C 26 A
Rated Operational Power AC-3 (Pe)
(400 V) 11 kW(415 V) 11 kW(440 V) 15 kW(500 V) 15 kW(690 V) 15 kW(380 / 400 V) 11 kW(220 / 230 / 240 V) 6.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 11 kW(440 V) 15 kW(500 V) 15 kW(690 V) 15 kW(380 / 400 V) 11 kW(220 / 230 / 240 V) 6.5 kW
Rated Operational Voltage
Main Circuit 690 V
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1
Terminal Type
Screw Terminals
Tightening Torque
Control Circuit 1.2 N·mMain Circuit 2.5 N·m
Wire Stripping Length
Control Circuit 10 mmMain Circuit 14 mm

Classifications

EClass
V11.0 : 27371003
ETIM 9
EC000066 - Power contactor, AC switching
Object Classification Code
Q

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 gOpen, Shock Direction: B1 5 gShock Direction: A 30 gShock Direction: B2 15 gShock Direction: C1 25 gShock Direction: C2 25 g
Resistance to Vibrations acc. to IEC 60068-2-6
5 ... 300 Hz 4 g closed position / 2 g open position
RoHS Information
2CMT2021-006277
WEEE Category
Product Not in WEEE Scope

Technical UL/CSA

Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 14-10 AWGRigid Stranded 1/2x 14-8 AWG
Continuous Current Rating NEMA
27 A
Full Load Amps Motor Use
(120 V AC) Single Phase 2 A(200 ... 208 V AC) Three Phase 7-1/2 A(220 ... 240 V AC) Three Phase 7-1/2 A(240 V AC) Single Phase 3 A(440 ... 480 V AC) Three Phase 15 A(550 ... 600 V AC) Three Phase 20 A
General Use Rating UL/CSA
(600 V AC) 45 A
Horsepower Rating NEMA
(115 V AC) Single Phase 2 Hp(200 V AC) Three Phase 7-1/2 Hp(230 V AC) Single Phase 3 Hp(230 V AC) Three Phase 7-1/2 Hp(460 V AC) Three Phase 10 Hp(575 V AC) Three Phase 10 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
NEMA Size
1
Tightening Torque UL/CSA
Control Circuit 11 in·lbMain Circuit 22 in·lb

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Product Main Type
AF26N1