Mersen

Q1019213

1 / 1
thumbnail

Descripción

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 6. These fuses are designed for “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
Country of Origin
IN
Part Number
Q1019213
UPC
3605340516982
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Specifications

Ampere Rating
20 A
Rated Voltage Ac Iec
550 V
Rated Voltage Dc Iec
250 V
Ac Max I R Breaking Capacity I1
80 kA
Product Diameter
0.53 in
Clearing I2T At Rated Voltage
1250 A²s
Melting I2T
250 A²s
Power Dissipation At Rated Current Value
1.7 W
Country Of Origin
IN
Product Line
Offset Blade fuse-links gG 550VAC/250VDC
Connection Terminal Material
Tin-Plated Copper
Connection Terminal Type
Plain Blades
Speed Characteristic
gG
Mounting
Clip
Max Rated Breaking Capacity Dc 1
40 kA