Type 3 surge protection device - MNT-NET B/F - 2882226
2882226
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
133,32 zł

Additional Information

Part Number
2882226
UPC
4046356073530
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for terminal equipment
Class Code : EC000942
Version : 7

Dimensions

Height
76 mm
Width
56 mm
Depth
79 mm

Connection data

Connection method
Grounding plug/socket

Ambient conditions

Degree of protection
IP20 (Child-proofing)
Ambient temperature (operation)
-25 °C - 75 °C
Ambient temperature (storage/transport)
-25 °C - 75 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Protective circuit

Nominal voltage UN
230/400 V AC (TN)
Nominal voltage UN
230/400 V AC (TT - only in use with RCD)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)
275 V AC
Maximum continuous operating voltage UC (L-PE)
360 V AC
Maximum continuous operating voltage UC (N-PE)
360 V AC
Rated load current IL
16 A (30 °C)
Residual current IPE
≤ 5 µA
Nominal discharge current In (8/20) µs
3 kA (> 5x)
Standby power consumption PC
≤ 1 VA
Reference test voltage UREF
255 V AC
Combination wave UOC
4 kV
Voltage protection level Up (L-N)
≤ 1.2 kV
Voltage protection level Up (L-PE)
≤ 1.5 kV
Voltage protection level Up (N-PE)
≤ 1.5 kV
TOV behavior at UT (L-N)
335 V AC (5 s / withstand mode)
TOV behavior at UT (L-N)
440 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE)
440 V AC (5 s / withstand mode)
TOV behavior at UT (L-PE)
440 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)
1455 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / safe failure mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (L-PE)
≤ 100 ns
Response time tA (N-PE)
≤ 100 ns
Max. required back-up fuse
16 A (gG / B / C)
Short-circuit current rating ISCCR
1.5 kA AC
Max. backup fuse with branch wiring
16 A (gG / B / C)

Standards and Regulations

Standards/specifications
IEC 61643-11 2011
Standards/specifications