Phoenix Contact
2905228
1 / 1
Descripción
Pluggable device protection, according to type 3/class III, for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with integrated surge-proof fuse and remote indication contact. Also suitable for DC applications.- Country of Origin
- DE
- Part Number
- 2905228
- Tariff Code
- 85363030
- EAN
- 4046356939690
- UPC
- 4046356939690
- ETIM
- Group Code : EG000021
- Group Description : Earthing, lightning and surge protection
- Class Description : Surge protection device for terminal equipment
- Class Code : EC000942
- Version : 7
$150.00
net1
Métodos de pago:
- Mejor oferta de:
- Proveedor de confianza de Automa.Net
- Disponibilidad:
- 1 piezaEn stockActualizado en: 07-11-2024
- Garantía:
- 12 meses
- Entrega Estimada:
- Bajo pedido
- Condición:
- Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía
UL indicator/remote signaling
- Tightening torque
- 5 lbf-in. - 7 lbf-in.
- Conductor cross section AWG
- 14 - 12
UL specifications
- SPD Type
- 4CA
- Maximum continuous operating voltage MCOV
- 150 V AC
- Maximum continuous operating voltage MCOV
- 150 V DC
- Nominal voltage
- 120 V DC
- Rated load current IL
- 25 A
- Mode of protection
- L-N
- Mode of protection
- L-G
- Mode of protection
- N-G
- Mode of protection
- (L+) - (L-)
- Mode of protection
- (L+) - G
- Mode of protection
- (L-) - G
- Power distribution system
- Single phase
- Nominal frequency
- 50/60 Hz
- Measured limiting voltage MLV (L-N)
- 780 V
- Measured limiting voltage MLV (L-G)
- 760 V
- Measured limiting voltage MLV (N-G)
- 760 V
- Measured limiting voltage MLV (L+) - (L-)
- 780 V
- Measured limiting voltage MLV (L+) - G
- 760 V
- Measured limiting voltage MLV (L-) - G
- 760 V
- Nominal discharge current In
- 3 kA
Dimensions
- Height
- 90 mm
- Width
- 17.7 mm
- Depth
- 74.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch
- 1 Div.
Connection data
- Connection method
- Screw connection
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section solid
- 0.2 mm² - 4 mm²
- Conductor cross section AWG
- 24 - 12
- Screw thread
- M3
- Tightening torque
- 0.8 Nm
- Stripping length
- 8 mm
Indicator/remote signaling
- Switching function
- N/C contact
- Operating voltage
- 250 V AC
- Operating voltage
- 125 V DC (200 mA DC)
- Operating current
- 3 A AC
- Operating current
- 1 A DC (30 V DC)
- Connection method
- Screw connection
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section solid
- 0.2 mm² - 4 mm²
- Conductor cross section AWG
- 24 - 12
- Screw thread
- M3
- Tightening torque
- 0.8 Nm
- Stripping length
- 8 mm
Ambient conditions
- Degree of protection
- IP20
- Ambient temperature (operation)
- -40 °C - 70 °C
- Ambient temperature (storage/transport)
- -40 °C - 70 °C
- Altitude
- ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation)
- 5 % - 95 %
- Shock (operation)
- 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
- Vibration (operation)
- 5g (10 - 150 Hz/20 cycles/axis/X, Y, Z)
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Protective circuit
- Nominal voltage UN
- 120 V AC (TN-S)
- Nominal voltage UN
- 120 V AC (TT - only in use with RCD)
- Nominal frequency fN
- 50 Hz (60 Hz)
- Maximum continuous voltage UC
- 150 V AC
- Maximum continuous voltage UC
- 150 V DC
- Rated load current IL
- 26 A (30 °C)
- Residual current IPE
- ≤ 5 µA
- Nominal discharge current In (8/20) µs
- 3 kA
- Standby power consumption PC
- ≤ 150 mVA (at UREF)
- Standby power consumption PC
- ≤ 175 mVA (at UC)
- Reference test voltage UREF
- 132 V AC
- Combination wave UOC
- 6 kV
- Voltage protection level Up (L-N)
- ≤ 0.85 kV
- Voltage protection level Up (L-PE)
- ≤ 0.95 kV
- Voltage protection level Up (N-PE)
- ≤ 0.95 kV
- TOV behavior at UT (L-N)
- 240 V AC (5 s / withstand mode)
- TOV behavior at UT (L-N)
- 240 V AC (120 min / withstand mode)
- TOV behavior at UT (L-PE)
- 240 V AC (5 s / withstand mode)
- TOV behavior at UT (L-PE)
- 240 V AC (120 min / withstand mode)
- TOV behavior at UT (L-PE)
- 1332 V AC (200 ms / safe failure mode)
- TOV behavior at UT (N-PE)
- 1200 V AC (200 ms / safe failure mode)
- Response time tA (L-N)
- ≤ 25 ns
- Response time tA (L-PE)
- ≤ 100 ns
- Response time tA (N-PE)
- ≤ 100 ns
- Short-circuit current rating ISCCR
- 1.5 kA AC
- Short-circuit current rating ISCCR
- 0.25 kA DC
- Max. backup fuse with branch wiring
- not required
- Maximum backup fuse for through wiring
- 25 A (gG / B / C)
Standards and Regulations
- Standards/specifications
- EN 61643-11 2012
UL connection data
- Conductor cross section AWG
- 14 - 12
- Tightening torque
- 5 lbf-in. - 7 lbf-in.
Otras categorías
ActuadoresBloquesCables, tuberías y manguerasCompresoresControlAcoplamientos y AccesoriosCilindros y PistonesElectrónicaFiltrosHVACPCs industriales y HMIsIluminaciónTécnica linealMotoresFuente de alimentaciónTransmisión de energíaBombas y VálvulasEnergías renovablesRobóticaSellos, anillos y conectoresSensores y dispositivos de mediciónHerramientas y AccesoriosCNCOtros