This product is part of the NEMA Pressure Switches range, an offer of mechanical alternators. This mechanical alternator has 4 normally closed, snap action, DPST-DB (double pole single throw, double break) form YY contacts. The open tank mechanical alternator supports pedestal mounting method and vertical float rod angle for operating in any position. It is furnished with screw clamp terminals for electrical connection and 2 conduit entries for 3/4-14 NPT. Offers electrical durability of 100 cycles and mechanical durability of 300 cycles. The enclosure is made of cast aluminum. It is a NEMA 4 rated product. This product is certified by UL, CSA, CE. Meets UL 508 standards. When liquid level rises to the first level, one pump turns on. Both pumps automatically turn on when a peak condition occurs and the liquid level continues to rise. If form N5 or N25 is present and the water level continues to rise. Mechanical alternator provides a simple, positive means of mechanically alternating two pumps or motors. This alternator is used on devices that are installed in a duplex system with a common tank. It is a NEMA 4 rated product. This product is certified by CE, CSA and UL. Meets UL 508 standards. When liquid level rises to the first level, one pump turns on. Both pumps automatically turn on when a peak condition occurs and the liquid level continues to rise. If form N5 or N25 is present and the water level continues to rise. Mechanical alternator provides a simple, positive means of mechanically alternating two pumps or motors. This alternator is used on devices that are installed in a duplex system with a common tank.
Country of Origin
MX
Part Number
9038AW1N5
Tariff Code
8536509065
EAN
39122219
UPC
785901173908
UNSPSC
39122219
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Specifications

Range Of Product
Square D Pumptrol
Product Specific Application
mechanically alternating the operation of two pumps or motors
Quantity Per Set
set of 1
Electrical Circuit Type
power circuit with control duty alarm
Product Or Component Type
mechanical alternator
Type Of Packing
individual
Device Application
open tank
Device Short Name
9038A

Contractual warranty

Warranty
18 months

Complementary

Cable Entry Number
2 conduit entries for 3/4"-14 NPT UL 508
Electrical Connection
screw-clamp terminals 10 AWG
Contact Operation
contacts close on liquid rise
Product Destination
for open tank
Terminal Block Type
8 terminals
Terminals Description Iso N°1
line-load-load-line
[Ui] Rated Insulation Voltage
575 V UL 508
Short-Circuit Protection
20 A cartridge fuse gG
Controlled Fluid
fresh water specific gravity of 0.85 in or higher || sea water specific gravity of 0.85 in or higher || hydraulic oil specific gravity of 0.85 in or higher || corrosive fluid specific gravity of 0.85 in or higher
Device Mounting
pedestal
Mechanical Durability
300 cycles
Float Rod Angle
vertical
Factory Modification
addition of a third, high-water alarm circuit (SPST-NO-DB)
Float Movement
variable adjustable
Operating Position
vertical position only
Enclosure Material
Cast Aluminium
Maximum Operating Rate
60 cyc/mn
Local Signalling
without
Contacts Type And Composition
4 NC, snap action, DPST-DB, Form YY
Motor Power Kw
1.5 kW 2 hp)115 V AC, 1 phase || 2.2 kW 3 hp)115 V AC, 3 phase || 2.2 kW 3 hp)230 V AC, 1 phase || 3.7 kW 5 hp)230 V AC, 3 phase || 0.75 kW 1 hp)460 V AC, 3 phase || 0.75 kW 1 hp)475 V AC, 3 phase || 0.18 kW 0.25 hp)32 V DC || 0.37 kW 0.5 hp)115 V DC || 0.37 kW 0.5 hp)230 V DC
Float Position
any
Kit Composition
float switch || rod and float are to be choosen in accessories
Electrical Durability
100 cycles 60 cyc/mn

Offer Sustainability

Circularity Profile
ENVEOLI111210EN
Environmental Disclosure
ENVPEP111211EN
Eu Rohs Directive
Not applicable, out of EU RoHS legal scope
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Environment

Product Certifications
UL listed file E12158 || CSA file LR25490
Ambient Air Temperature For Operation
-22-220 °F
Ambient Air Temperature For Storage
-22-220 °F
Standards
CE || UL 508
Nema Degree Of Protection
NEMA 4 UL 50

Documentos

Data Sheet

Descargar