- Output Coupling
- parallel || serial
- Height
- 30 mm
- Residual Ripple
- < 150 mV
- Status Led
- 1 LED (Green) output voltage
- Holding Time
- > 20 ms 115 V AC || > 40 ms 230 V AC
- Efficiency At Full Load
- 90...264 V AC
- Earthing System
- TN || TT || IT
- Connections - Terminals
- screw connection 0.75...2.5 mm², AWG 18...AWG 14) without wire end ferrule || screw connection 0.75...1.5 mm², AWG 18...AWG 16) with wire end ferrule
- Dielectric Strength
- 3750 V AC with input to output
- Network Frequency Limits
- 50-60 Hz
- Current Consumption
- < 2.3 A 115 V AC || < 1.5 A 230 V AC
- Supply
- SELV IEC 60950-1 || SELV IEC 60204-1 || SELV IEC 60364-4-41
- Net Weight
- 0.3 kg
- Maximum Leakage Current
- 1 mA 240 V AC
- Input Protection Type
- integrated fuse (not interchangeable) 4 A
- Output Protection Type
- against overload and short-circuits automatic reset || against over temperature manual reset || against overvoltage manual reset
- Service Life
- 10 year(s)
- Meantime Between Failure [Mtbf]
- 700000 h at 25 °C, full load conforming to SR 332
- Power Dissipation In W
- 20 W
- Output Voltage Limits
- 21.6...26.4 V
- Mounting Support
- top hat type TH35-15 rail IEC 60715 || top hat type TH35-7.5 rail IEC 60715 || double-profile DIN rail || panel mounting
- Load Capacitance
- 4000 µF
- Response Time
- < 500 ms
- Line And Load Regulation
- < 0.5 % network 0 to 100 % load at 25 °C || < 1 % network full voltage range in line at 25 °C
- Width
- 97 mm
- Overvoltage Category
- II
- Inrush Current
- 45 A 115 V || 85 A 230 V
- Efficiency
- 89 % 230 V AC
- Depth
- 129 mm
- Power Factor
- 0.55 at 115 V AC || 0.45 at 230 V AC