BCPM power monitoring intermediate - 24 solid core 100 A - 18 mm CT spacing
BCPMB224S
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Oferta con plazo de entrega del fabricante
Entrega:1 - 2 días laborables
El mejor precio:
€814.64

Additional Information

Part Number
BCPMB224S
UNSPSC
83101808
Tariff Code
9028300000

Environment

Height
146 mm
Standards
IEC 61036 || ANSI C12.1 || UL 508 || EN 61010
Mounting Support
panel || enclosure
Product Certifications
UL
Net Weight
1.5 kg
Mounting Mode
panel-mounted
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
0-95 % 0-60 °C
Width
288 mm
Operating Altitude
9842.52 ft (3000 m)

Specifications

Network Frequency
50 Hz || 60 Hz
Power Quality Analysis
voltage sag and swell detection
Variant
intermediate
Type Of Measurement
voltage || current || frequency || active power || power factor || active energy
Power Monitoring
basic instrumentation
Product Or Component Type
multi-circuit energy meter
Product Name
PowerLogic BCPM
Range
PowerLogic
Energy Management
sub billing and cost allocation
[Us] Rated Supply Voltage
90...277 V AC 50/60 Hz +/- 1 %
Device Application
sub billing
Device Short Name
BCPMB

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Compliant with Exemptions

Complementary

Communication Port Support
RS485
Connection Pitch
18 mm
Measurement Voltage
90-277 V phase to neutral || 150-480 V phase to phase
Sampling Rate
256 samples/cycle
Communication Port Protocol
Modbus RTU
Communication Of Data
high-high current alarm || over voltage alarm || under voltage alarm || high current alarm || low-low current alarm || low current alarm
Provided Equipment
24 x current transformer
Measurement Accuracy
branch current 2 % 0.25…2 A || branch current 1 % 2…100 A || mains current 3 % 1…100 % || mains current 3 % 2…100 % || voltage 1 % 90…277 V
Update Time
1.8 s
Analogue Input Type
solid core CT 100 A24 x