1 / 5
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail

Descripción

Activo maduro
PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 35kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 90A, 2 pole, circuit breaker has a breaking capacity of 35kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with an AB phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
Part Number
BGA24090Y1
Tariff Code
8536200010
UPC
785901459095
UNSPSC
39121601
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Specifications

Product Or Component Type
circuit breaker
Product Name
PowerPact B
Range
PowerPact
Device Application
distribution
Device Short Name
BG 090

Complementary

Mounting Mode
I-Line
Network Frequency
50/60 Hz
[Ics] Rated Service Breaking Capacity
65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology
thermal-magnetic
Height
137 mm
Connection Pitch
27 mm
[Ue] Rated Operational Voltage
525 V AC 50/60 Hz UL 489
Tightening Torque
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
Breaking Capacity Code
G
9 Mm Pitches
6
Local Signalling
presence of auxiliary contacts flag green)
Number Of Slots
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
Electrical Connection
I-Line connection, line || lugs, load
Mounting Height
76.2 mm
Net Weight
0.952 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Control Type
toggle
Circuit Breaker Application
HACR rated
Wire Stripping Length
20 mm
Line Rated Current
90-90 A
Utilisation Category
category A
Continuous Current Rating
80 %
Breaking Capacity
65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489
[Ui] Rated Insulation Voltage
800 V IEC 60947-2
Mechanical Durability
20000 cycles IEC 947-1 Annex K ed 5.2
Suitability For Isolation
yes IEC 60947-2
Electrical Durability
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Poles Description
2P
Quantity Per Set
set of 1
Awg Gauge
AWG 14...AWG 2/0 aluminium/copper
Color
Gray RAL 7016)
Width
54 mm
Depth
89 mm
Phase Connection
AB

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1610005EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
N/A
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free product

Environment

Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
UL 489 || NEMA AB1 || EN/IEC 60947-2 || CSA C22.2 No 5 || NMX J-266 || GB 14048.2 || EN/IEC 60947-5-1
Product Certifications
UL || IEC || CCC || EAC || CSA || NOM
Ip Degree Of Protection
front cover IP40 IEC 60529
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-50-85 °C
Quality Labels
CE
Operating Altitude
< 6561.68 ft (2000 m) without derating || 5000 m with derating

Documentos

Data Sheet

Descargar