- Product Certifications
- CB Scheme || UL || CSA || EAC || CE || UKCA
- [Ue] Rated Operational Voltage
- 1000 V AC 25...200 Hz
- Power Dissipation Per Pole
- 22 W AC-3 || 39 W AC-1
- Average Impedance
- 0.32 mOhm - Ith 350 A 50 Hz
- Standards
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || JIS C8201-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Control Circuit Type
- AC 50...400 Hz || DC standard
- [Uc] Control Circuit Voltage
- 220...230 V AC 50...400 Hz || 220...230 V DC
- Contactor Application
- resistive load || motor control
- Rated Breaking Capacity
- 2450 A at 220...440 V || 2200 A at 500 V || 800 A at 1000 V || 1700 A at 660/690 V
- Product Or Component Type
- magnetic latching contactor
- Irms Rated Making Capacity
- 2940 A
- Product Name
- TeSys F
- Associated Fuse Rating
- 315 A aM at <= 440 V || 400 A BS88 at <= 440 V || 400 A gG at <= 440 V
- Connections - Terminals
- lugs-ring terminals 1 240-240 mm² || connector 1 240-240 mm² || bars 2 32 x 4 mm || power circuit bolted connection
- Range
- TeSys
- Pole Contact Composition
- 3 NO
- Utilisation Category
- AC-4 || AC-3 || AC-1
- [Ie] Rated Operational Current
- 265 A (at <40 °C) at <= 440 V AC AC-3 || 350 A (at <40 °C) at <= 440 V AC AC-1 || 245 A (at <40 °C) at <= 440 V AC AC-4
- Maximum Operating Rate
- 120 cyc/h 40 °C
- Tightening Torque
- 35 N.m
- Mechanical Durability
- 1 Mcycles
- Poles Description
- 3P
- Operating Time
- 40...75 ms latching || 50...100 ms unlatching
- Motor Power Kw
- 132 kW at 400 V AC 50/60 Hz (AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60158-1 || 1000 V IEC 60947-4 || 1000 V BS 775 || 1500 V VDE 0110 group C
- Device Application
- control
- Device Short Name
- CR1F
- [Icw] Rated Short-Time Withstand Current
- 2200 A 40 °C - 1 s || 2200 A 40 °C - 5 s || 2200 A 40 °C - 10 s || 1230 A 40 °C - 30 s || 950 A 40 °C - 1 min || 620 A 40 °C - 3 min || 480 A 40 °C - 10 min