1 / 1
thumbnail

Descripción

Activo maduro
LC2D32BD is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 32A AC-3 15kW@400V, it includes a 24V DC coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D32BD is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 15kW@400V. It includes a 24V DC coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 24V DC coil for easy integration to all control systems. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 32A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.
Country of Origin
FR
Part Number
LC2D32BD
Tariff Code
85364900
EAN
3389110392784
UNSPSC
39121529
Métodos de pago:
Mejor oferta de:
ITProveedor de confianza de Automa.Net
Disponibilidad:
275 piezas
En stock
Actualizado en: 09-11-2024
Garantía:
12 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevo Precintado de Fábrica
Nuevo Precintado de Fábrica - Un artículo completamente nuevo, sin usar, sin abrir, sin daños, en su embalaje original sellado por el fabricante.
Un total de 1183 Parts In-Stock de 7 Distributors
Información de envío
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Ofertas Disponibles (6)

LC2D32BD product image
Schneider Electric

LC2D32BD

Condición:
Nuevos excedentes
Disponible:
393 piezas
En stock
Actualizado en: 08-11-2024
Oferta de:
FRProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
€263.94
net
LC2D32BD product image
Schneider Electric

LC2D32BD

Condición:
Nuevos excedentes
Disponible:
3 piezas
En stock
Actualizado en: 09-11-2024
Oferta de:
USProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
$789.75
net
LC2D32BD product image
Schneider Electric

LC2D32BD

Condición:
Nuevos excedentes
Disponible:
1 pieza
En stock
Actualizado en: 21-10-2024
Oferta de:
GBProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
1
LC2D32BD product image
Schneider Electric

LC2D32BD

Condición:
Nuevos excedentes
Disponible:
1 pieza
En stock
Actualizado en: 08-11-2024
Oferta de:
DEProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
LC2D32BD product image
Schneider Electric

LC2D32BD

Condición:
Nuevos excedentes
Disponible:
255 piezas
En stock
Actualizado en: 08-11-2024
Oferta de:
FRProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
12 meses
1
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
€120.81

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
Ambient Air Temperature For Operation
-40-60 °C || 60-70 °C with derating
Height
85 mm
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
Net Weight
1.127 kg
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
90 mm
Depth
101 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110230EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1102030EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Control Circuit Voltage Limits
0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Hold-In Power Consumption In W
5.4-5.4 W 20 °C
Insulation Resistance
> 10 MOhm for signalling circuit
Coil Technology
built-in bidirectional peak limiting diode suppressor
Time Constant
28 ms
Minimum Switching Voltage
17 V for signalling circuit
Signalling Circuit Frequency
25...400 Hz
Inrush Power In W
5.4-5.4 W 20 °C)
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1

Specifications

Product Certifications
UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
24 V DC
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole
2 W AC-3 || 5 W AC-1 || 2 W AC-3e
Average Impedance
2 mOhm - Ith 50 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 50 A (at 60 °C) for power circuit
Mounting Support
rail || plate
Control Circuit Type
DC standard
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
motor control || resistive load
Rated Breaking Capacity
550 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type
reversing contactor
Irms Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Product Name
TeSys D || TeSys Deca
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid || power circuit screw clamp terminals 2 2.5-10 mm²solid
Range
TeSys || TeSys Deca
Pole Contact Composition
3 NO
Device Presentation
preassembled with reversing power busbar
Utilisation Category
AC-1 || AC-3 || AC-3e
[Ie] Rated Operational Current
32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V
Mechanical Durability
30 Mcycles
Poles Description
3P
Operating Time
53.55...72.45 ms closing || 16...24 ms opening
Overvoltage Category
III
Motor Power Kw
7.5 kW at 220...230 V AC 50-60 Hz || 15 kW at 380...400 V AC 50-60 Hz || 15 kW at 415 V AC 50-60 Hz || 15 kW at 440 V AC 50-60 Hz || 18.5 kW at 500 V AC 50-60 Hz || 18.5 kW at 660...690 V AC 50-60 Hz
Maximum Horse Power Rating
2 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 20 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short Name
LC2D
[Icw] Rated Short-Time Withstand Current
60 A 40 °C - 10 min for power circuit || 138 A 40 °C - 1 min for power circuit || 260 A 40 °C - 10 s for power circuit || 430 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover
with

Modelos CAD

traceparts
traceparts
Descargar