- [Ics] Rated Service Breaking Capacity
- 10 kA 600...690 V IEC 60947-2 || 35 kA 480...525 V IEC 60947-2 || 50 kA <= 440 V IEC 60947-2
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- [Uc] Control Circuit Voltage
- 24 V DC
- Height
- 243 mm
- Control Circuit Voltage Limits
- 0.25...0.7 Uc drop-out 55 °C || 0.85...1.1 Uc operation 55 °C
- [Ith] Conventional Free Air Thermal Current
- 63 A 40 °C
- Maximum Breaking Time
- 4 ms
- Hold-In Power Consumption In W
- 8-8 W 20 °C
- Irms Rated Making Capacity
- 756 A IEC 60947-4 || 946 A IEC 60947-4
- Net Weight
- 3.8 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-4
- Connections - Terminals
- power circuit screw clamp terminals 1 6-50 mm² flexible - without cable end || power circuit screw clamp terminals 2 6-25 mm² flexible - without cable end || power circuit screw clamp terminals 1 6-25 mm² flexible - with cable end || power circuit screw clamp terminals 2 6-25 mm² flexible - with cable end || power circuit screw clamp terminals 1 6-50 mm² solid
- Thermal Stress Limit
- 300000 A².s
- Utilisation Category
- AC-43 || AC-1
- [Ie] Rated Operational Current
- 63 A AC AC-1 || 63 A AC AC-43
- Electrical Durability
- 1 Mcycles AC-3 3 kA 415 V - after 1 cycle O-CO-r-CO at Isc || 0.9 Mcycles AC-3 10 kA 415 V - after 1 cycle O-CO-r-CO at Isc || 0.6 Mcycles AC-3 25 kA 415 V - after 1 cycle O-CO-r-CO at Isc || 0.5 Mcycles AC-3 35 kA 415 V - after 1 cycle O-CO-r-CO at Isc || 0.2 Mcycles AC-3 50 kA 415 V - after 1 cycle O-CO-r-CO at Isc
- Breaking Capacity
- Icu 10 kA 600...690 V 0.5 ) IEC 60947-2 || Icu 30 kA 480...525 V 0.25 ) IEC 60947-6-2 || Icu 50 kA <= 440 V 0.25 ) IEC 60947-2
- Operating Time
- 15...25 ms DC opening 20 °C control circuit || 25...40 ms DC closing 20 °C control circuit
- [Ui] Rated Insulation Voltage
- 690 V IEC 60947-1
- Tightening Torque
- power circuit 6 N.m screw clamp terminals
- Control Type
- knob emergency stop Red front CNOMO
- Mechanical Durability
- 1.2 Mcycles
- Inrush Power In W
- 300-300 W 20 °C)
- Poles Description
- 3P
- [Ipk] Rated Peak Withstand Current
- 105 kA IEC 60947-2
- Test Function
- self test
- Width
- 90 mm
- Depth
- 192 mm
- Motor Power Kw
- 15 kW 220...240 V AC 50/60 Hz || 30 kW 400 V AC 50/60 Hz || 33 kW 415 V AC 50/60 Hz || 37 kW 500 V AC 50/60 Hz || 55 kW 660 V AC 50/60 Hz || 33 kW 440 V AC 50/60 Hz
- Heat Dissipation
- 5-5 W 32 A per pole, hot state power circuit || 7-7 W 50 A per pole, hot state power circuit || 9-9 W 63 A per pole, hot state power circuit || 4.4-4.4 W 25 A per pole, hot state power circuit || 5.8-5.8 W 40 A per pole, hot state power circuit