Schneider Electric
LV433316
Circuit breaker, ComPact NSX100HB1, 75kA/690VAC, MicroLogic 6.2E-M trip unit 50A, 3 poles 3d
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
Enviar solicitud de precio
1
Formas de pago:
Condiciones del producto:
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
€1,546.08
Additional Information
- Part Number
- LV433316
- Country of Origin
- FR
Specifications
- Network Frequency
- 50/60 Hz
- Line Rated Current
- 50 A 65 °C
- Trip Unit Name
- MicroLogic 6.2 E-M
- Range Of Product
- ComPact NSX100...250
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSIG
- Network Type
- AC
- Protected Poles Description
- 3t
- Product Or Component Type
- circuit breaker
- Product Name
- ComPact NSX
- Range
- ComPact
- Control Type
- toggle
- Utilisation Category
- category A
- Mounting Mode
- fixed
- Breaking Capacity
- 85 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 75 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 3P
- Breaking Capacity Code
- HB1 75 kA 690 V AC
- Device Application
- motor
- Device Short Name
- NSX100HB1
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Tg] Ground-Fault Time Delay Adjustment Range
- 0-0.4 s
- [Ics] Rated Service Breaking Capacity
- 85 kA 500 V AC 50/60 Hz IEC 60947-2 || 80 kA 525 V AC 50/60 Hz IEC 60947-2 || 75 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Height
- 161 mm
- [Ig] Ground-Fault Pick-Up Adjustment Range
- 0.3...1 x In || Ig enable on/off
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Ground-Fault Time Delay Adjustment Type -Tg
- adjustable 5 settings
- Mounting Support
- backplate
- Complementary Motor Protection
- stalled rotor || underload || phase unbalance || protracted starting time
- Ground-Fault Pick-Up Adjustment Type
- adjustable 9 settings
- Instantaneous Pick-Up Adjustment Range
- 750 A
- Type Of Measurement
- energy meter
- Downside Connection
- front
- Number Of Slots
- 5
- Communication Of Data
- maximeters/minimeters || protection and alarm settings || demand current and power || maintenance indicators || power quality || phase sequence || time-stamped histories and event tables || energy metering || thermal image function || instantaneous and demand values
- Protection Type
- L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
- Long Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Type Ii
- fixed
- Zone Selective Interlocking Zsi
- with
- Net Weight
- 2.05 kg
- [Tr] Long-Time Delay Adjustment Range
- 10-10 s 7.2 x Ir 10 || 120-120 s 1.5 x Ir 5 || 20-20 s 7.2 x Ir 20 || 240-240 s 1.5 x Ir 10 || 26-26 s 6 x Ir 20 || 480-480 s 1.5 x Ir 20 || 5-5 s 7.2 x Ir 5 || 13.5-13.5 s 6 x Ir 10 || 6.5-6.5 s 6 x Ir 5 || 30-30 s 7.2 x Ir 30 || 38-38 s 6 x Ir 30 || 720-720 s 1.5 x Ir 30
- Electrical Durability
- 10000 cycles 690 V In || 20000 cycles 690 V In/2 || 30000 cycles 440 V In || 50000 cycles 440 V In/2
- Short-Time Delay Adjustment Type
- fixed
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 25...50 A
- Upside Connection
- front
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- Trip Unit Rating
- 50-50 A 65 °C
- Local Signalling
- for ready to operate flashing LED (green) || for temperature over set point LED 95 % Ith (red)
- Mechanical Durability
- 50000 cycles
- Motor Tripping Class
- 10 || 5 || 20 || 30
- [Isd] Short-Time Pick-Up Adjustment Range
- 5...13 x Ir
- Connection Pitch
- 35 mm
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Width
- 105 mm
- Display Type
- LCD display
- Depth
- 86 mm
- Short-Time Pick-Up Adjustment Type Isd
- adjustable
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- CCC || EAC || Marine
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Electrical Shock Protection Class
- class II
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 0-95 %
- Operating Altitude
- 0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
- Overvoltage Category
- class II
Documentos
Data Sheet
DescargarModelos CAD
traceparts
Descargar