Descripción

This Compact NSX100HB2 is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 100kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 5.2 E trip unit, with 40A rating. Micrologic 5.2 E trip unit provides adjustable long time, short time and instantaneous protection. Micrologic 5.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX100HB2 is part of Schneider Electric EcoStruxure Power architecture.
Country of Origin
FR
Part Number
LV433338
Tariff Code
85362010
EAN
3606480479717
UNSPSC
39121601
Métodos de pago:
Mejor oferta de:
DEProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 08-11-2024
Garantía:
12 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Specifications

Network Frequency
50/60 Hz
Line Rated Current
40 A 40 °C
Trip Unit Name
Micrologic 5.2 E
Range Of Product
ComPact NSX100...250
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LSI
Network Type
AC
Protected Poles Description
3t || 3t + OSN || 4t || 3t + N/2
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
4P
Breaking Capacity Code
HB2 100 kA 690 V AC
Neutral Position
left
Device Application
distribution
Device Short Name
NSX100HB2
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

[Ics] Rated Service Breaking Capacity
100 kA 500 V AC 50/60 Hz IEC 60947-2 || 100 kA 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height
161 mm
Thermal Memory
20 minutes before and after tripping
Earth-Leakage Protection
without
Mounting Support
backplate
Instantaneous Pick-Up Adjustment Range
1.5...15 x In
Type Of Measurement
energy meter
Downside Connection
front
Number Of Slots
5
Communication Of Data
time-stamped histories and event tables || protection and alarm settings || maximeters/minimeters || energy metering || power quality || demand current and power || maintenance indicators || instantaneous and demand values
Protection Type
L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection
Long Time Delay Adjustment Type
adjustable
Instantaneous Pick-Up Adjustment Type Ii
adjustable
Zone Selective Interlocking Zsi
with
Net Weight
2.4 kg
[Tr] Long-Time Delay Adjustment Range
15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
Electrical Durability
10000 cycles 690 V In || 20000 cycles 690 V In/2 || 30000 cycles 440 V In || 50000 cycles 440 V In/2
Short-Time Delay Adjustment Type
adjustable
Long Time Pick-Up Adjustment Type Ir
adjustable 9 settings
Long Time Pick-Up Adjustment Range
18...40 A
Upside Connection
front
[Tsd] Short-Time Delay Adjustment Range
0-0.4 s
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
40-40 A 40 °C
Local Signalling
for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
Mechanical Durability
50000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
1.5...10 x Ir
Connection Pitch
35 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
140 mm
Display Type
LCD display
Depth
86 mm
Short-Time Pick-Up Adjustment Type Isd
adjustable 9 settings

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
CCC || EAC || Marine
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II

Modelos CAD

traceparts
traceparts
Descargar