1 / 1
thumbnail

Descripción

This Compact NSX400HB1 is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 2.3 trip unit, with 250A rating. Micrologic 2.3 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 4 poles version (185mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX400HB1 is part of Schneider Electric EcoStruxure Power architecture.
Country of Origin
FR
Part Number
LV433621
Tariff Code
85362090
EAN
3606480480898
UNSPSC
39121601
Métodos de pago:
Mejor oferta de:
DEProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 08-11-2024
Garantía:
12 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Specifications

Network Frequency
50/60 Hz
Line Rated Current
250 A 40 °C
Trip Unit Name
Micrologic 2.3
Range Of Product
ComPact NSX400...630
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LSoI
Network Type
AC
Protected Poles Description
3t || 4t || 3t + N/2
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
85 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 75 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
4P
Breaking Capacity Code
HB1 75 kA 690 V AC
Neutral Position
left
Device Application
distribution
Device Short Name
NSX400HB1
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

[Ics] Rated Service Breaking Capacity
85 kA 500 V AC 50/60 Hz IEC 60947-2 || 80 kA 525 V AC 50/60 Hz IEC 60947-2 || 75 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height
255 mm
Thermal Memory
20 minutes before and after tripping
Earth-Leakage Protection
without
Mounting Support
backplate
Instantaneous Pick-Up Adjustment Range
3000 A
Downside Connection
front
Number Of Slots
6
Protection Type
L : for overload protection (long time) || So : for short time short-circuit protection with fixed delay || I : for instantaneous short-circuit protection
Long Time Delay Adjustment Type
fixed
Instantaneous Pick-Up Adjustment Type Ii
fixed
Zone Selective Interlocking Zsi
without
Net Weight
7.9 kg
[Tr] Long-Time Delay Adjustment Range
11-11 s 7.2 x Ir || 16-16 s 6 x Ir || 400-400 s 1.5 x Ir
Electrical Durability
3000 cycles 690 V In || 6000 cycles 690 V In/2 || 6000 cycles 440 V In || 12000 cycles 440 V In/2
Short-Time Delay Adjustment Type
fixed
Neutral Protection Setting
0.5 x Ir 3t + N/2) || 1 x Ir 4t) || no protection 3t)
Long Time Pick-Up Adjustment Type Ir
adjustable 9 settings
Long Time Pick-Up Adjustment Range
70...250 A
Upside Connection
front
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
250-250 A 40 °C
Local Signalling
for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
Mechanical Durability
15000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
1.5...10 x Ir
Connection Pitch
45 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
185 mm
Depth
110 mm
Short-Time Pick-Up Adjustment Type Isd
adjustable 9 settings

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
Marine || EAC || CCC
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-50-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II

Modelos CAD

traceparts
traceparts
Descargar