Schneider Electric
LV433629
1 / 1
Descripción
This Compact NSX400HB1 is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 400A rating electronic Micrologic 6.3 E trip unit, with an adjustable ground-fault protection (with OFF position). Micrologic 6.3 E trip unit provides adjustable long time, short time and instantaneous protection. Micrologic 6.3 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 4 poles version (185mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX400HB1 is part of Schneider Electric EcoStruxure Power architecture.- Country of Origin
- FR
- Part Number
- LV433629
- Tariff Code
- 85362090
- EAN
- 3606480480973
- UNSPSC
- 39121601
Métodos de pago:
- Mejor oferta de:
- Proveedor de confianza de Automa.Net
- Disponibilidad:
- 1 piezaEn stockActualizado en: 08-11-2024
- Garantía:
- 12 meses
- Entrega Estimada:
- Bajo pedido
- Condición:
- Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía
Specifications
- Network Frequency
- 50/60 Hz
- Line Rated Current
- 400 A 40 °C
- Trip Unit Name
- Micrologic 6.3 E
- Range Of Product
- ComPact NSX400...630
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSIG
- Network Type
- AC
- Protected Poles Description
- 3t + OSN || 4t || 3t + N/2 || 3t
- Product Or Component Type
- circuit breaker
- Product Name
- ComPact NSX
- Range
- ComPact
- Control Type
- toggle
- Utilisation Category
- category A
- Mounting Mode
- fixed
- Breaking Capacity
- 85 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 75 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 4P
- Breaking Capacity Code
- HB1 75 kA 690 V AC
- Neutral Position
- left
- Device Application
- distribution
- Device Short Name
- NSX400HB1
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Tg] Ground-Fault Time Delay Adjustment Range
- 0-0.4 s I²t=off || 0.1-0.4 s I²t=on
- [Ics] Rated Service Breaking Capacity
- 85 kA 500 V AC 50/60 Hz IEC 60947-2 || 80 kA 525 V AC 50/60 Hz IEC 60947-2 || 75 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Height
- 255 mm
- [Ig] Ground-Fault Pick-Up Adjustment Range
- 0.2...1 x In || Ig enable on/off
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Ground-Fault Time Delay Adjustment Type -Tg
- adjustable 5 settings
- Mounting Support
- backplate
- Ground-Fault Pick-Up Adjustment Type
- adjustable 9 settings
- Instantaneous Pick-Up Adjustment Range
- 1.5...12 x In
- Type Of Measurement
- energy meter
- Downside Connection
- front
- Number Of Slots
- 6
- Communication Of Data
- demand current and power || time-stamped histories and event tables || protection and alarm settings || energy metering || maximeters/minimeters || maintenance indicators || power quality || instantaneous and demand values
- Protection Type
- L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
- Long Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Type Ii
- adjustable
- Zone Selective Interlocking Zsi
- with
- Net Weight
- 7.9 kg
- [Tr] Long-Time Delay Adjustment Range
- 15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
- Electrical Durability
- 3000 cycles 690 V In || 6000 cycles 690 V In/2 || 6000 cycles 440 V In || 12000 cycles 440 V In/2
- Short-Time Delay Adjustment Type
- adjustable 5 settings
- Neutral Protection Setting
- 0.5 x Ir 3t + N/2) || 1 x Ir 4t) || 1.6 x Ir 3t + OSN) || no protection 3t)
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 160...400 A
- Upside Connection
- front
- [Tsd] Short-Time Delay Adjustment Range
- 0-0.4 s
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- Trip Unit Rating
- 400-400 A 40 °C
- Local Signalling
- for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
- Mechanical Durability
- 15000 cycles
- [Isd] Short-Time Pick-Up Adjustment Range
- 1.5...12 x In
- Connection Pitch
- 45 mm
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Width
- 185 mm
- Display Type
- LCD display
- Depth
- 110 mm
- Short-Time Pick-Up Adjustment Type Isd
- adjustable
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- EAC || CCC || Marine
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Electrical Shock Protection Class
- class II
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -40-85 °C
- Relative Humidity
- 0-95 %
- Operating Altitude
- 0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
- Overvoltage Category
- class II