- [Tg] Ground-Fault Time Delay Adjustment Range
- 0-0.4 s I²t=off || 0.1-0.4 s I²t=on
- [Ics] Rated Service Breaking Capacity
- 100 kA 500 V AC 50/60 Hz IEC 60947-2 || 100 kA 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Height
- 255 mm
- [Ig] Ground-Fault Pick-Up Adjustment Range
- 0.2...1 x In || Ig enable on/off
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Ground-Fault Time Delay Adjustment Type -Tg
- adjustable 5 settings
- Mounting Support
- backplate
- Ground-Fault Pick-Up Adjustment Type
- adjustable 9 settings
- Instantaneous Pick-Up Adjustment Range
- 1.5...12 x In
- Type Of Measurement
- energy meter
- Downside Connection
- front
- Number Of Slots
- 6
- Communication Of Data
- demand current and power || energy metering || maximeters/minimeters || maintenance indicators || power quality || protection and alarm settings || time-stamped histories and event tables || instantaneous and demand values
- Protection Type
- L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
- Long Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Type Ii
- adjustable
- Zone Selective Interlocking Zsi
- with
- Net Weight
- 6.05 kg
- [Tr] Long-Time Delay Adjustment Range
- 15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
- Electrical Durability
- 3000 cycles 690 V In || 6000 cycles 690 V In/2 || 6000 cycles 440 V In || 12000 cycles 440 V In/2
- Short-Time Delay Adjustment Type
- adjustable 5 settings
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 160...400 A
- Upside Connection
- front
- [Tsd] Short-Time Delay Adjustment Range
- 0-0.4 s
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- Trip Unit Rating
- 400-400 A 40 °C
- Local Signalling
- for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
- Mechanical Durability
- 15000 cycles
- [Isd] Short-Time Pick-Up Adjustment Range
- 1.5...12 x In
- Connection Pitch
- 45 mm
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Width
- 140 mm
- Display Type
- LCD display
- Depth
- 110 mm
- Short-Time Pick-Up Adjustment Type Isd
- adjustable