- [Ics] Rated Service Breaking Capacity
- 50 kA 220/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 440 V AC 50/60 Hz IEC 60947-2 || 42 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 42 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Line Rated Current
- 1600 A 40 °C
- Connection Pitch
- 70 mm
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Mounting Support
- base plate || rails
- Circuit Breaker Ct Rating
- 1600 A || 630 A || 400 A || 800 A || 1250 A || 1000 A
- Maximum Breaking Time
- 25-25 ms
- Depth
- drawout circuit breaker without chassis 207.5 mm || drawout circuit breaker with chassis 266 mm
- Control Type
- push-button
- Maximum Closing Response Time
- 50 ms
- Mounting Mode
- drawout
- Breaking Capacity
- 50 kA Icu 220/415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 500/525 V AC 50/60 Hz IEC 60947-2 || 42 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
- [Icm] Rated Short-Circuit Making Capacity
- 105 kA 220/415 V AC 50/60 Hz || 105 kA 440 V AC 50/60 Hz || 88 kA 500/525 V AC 50/60 Hz || 88 kA 660/690 V AC 50/60 Hz
- Electrical Durability
- 3000 cycles 690 V AC 50/60 Hz IEC 60947-2 || 6000 cycles 440 V AC 50/60 Hz IEC 60947-2 || AC-23A 3000 cycles 690 V AC 50/60 Hz IEC 60947-3 || AC-23A 6000 cycles 440 V AC 50/60 Hz IEC 60947-3 || AC-3 6000 cycles 440 V AC 50/60 Hz IEC 60947-3
- [Ui] Rated Insulation Voltage
- 1000 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability
- 12500 cycles with periodic preventive maintenance IEC 60947-2
- Height
- drawout circuit breaker without chassis 259.5 mm || drawout circuit breaker with chassis 322 mm
- Width
- drawout circuit breaker without chassis 306.5 mm || drawout circuit breaker with chassis 358 mm
- Integral Instant Protection
- 81-99 kA
- [Uimp] Rated Impulse Withstand Voltage
- 12 kVIEC 60947-2
- [Icw] Rated Short-Time Withstand Current
- 42 kA 0.5 s IEC 60947-2 || 42 kA 1 s IEC 60947-2 || 24 kA 3 s IEC 60947-2