Schneider Electric
LZ1H6X5FU
1 / 1
Descripción
Activo maduro
TeSys H ultra compact direct starter, 3 poles, 6.5A/500V AC-53, for control and protection of 3-phase motors up to 3kW@400V (3HP@480V). The hybrid technology used for power contacts procures ultra compactness (22.5mm width) as well as an extended electrical durability up to 30 million cycles AC-53. It provides control for one direction of rotation, an adjustable motor current 1.5-6.5A, class 10A thermal overload protection with auto/manual/remote reset, phase loss and phase unbalanced protection, stall and jam motor protection. To be supplied with 110-230V AC, it provides logic inputs for ON/OFF motor running and remote reset after thermal tripping, 1C/O contact relay for fault indication, LED status on front face for indication of tripping and motor running. DIN rail mounting, screw terminals for control and power, it can be used for ambient temperatures from -25 to 70°C, without derating until 30°C. Multi standards certified (IEC, UL, CCC), Green Premium compliant (RoHS/REACh).- Country of Origin
- DE
- Part Number
- LZ1H6X5FU
- Tariff Code
- 85371098
- EAN
- 3606485421155
- UNSPSC
- 39121521
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
Enviar solicitud de precio
1
Formas de pago:
Specifications
- [Uc] Control Circuit Voltage
- 110...230 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- 500 V AC
- Thermal Protection Adjustment Range
- 1.5-9 A
- Product Or Component Type
- ultra-compact starter
- Product Name
- TeSys Hybrid
- Thermal Overload Class
- class 10A IEC 60947-4-2
- Motor Power Kw
- 1.5 kW 220 V AC 0.65 || 1.5 kW 230 V AC 0.65 || 2.2 kW 380 V AC 0.65 || 3 kW 400 V AC 0.65 || 3 kW 415 V AC 0.65 || 3 kW 440 V AC 0.65 || 3 kW 500 V AC 0.65
- Range
- TeSys
- Motor Starter Type
- direct on line
- [Ie] Rated Operational Current
- 6.5 A 500 V AC-53A || 9 A 500 V AC-51 || 4.5 A 500 V AC-53A mounting side by side || 6 A 500 V AC-51 mounting side by side
- Poles Description
- 3P
- Maximum Horse Power Rating
- 1 hp 200 V AC || 1.5 hp 230 V AC || 3 hp 460 V AC
- Device Short Name
- LZ1H
Complementary
- Height
- 99 mm
- Reset
- manual || automatic reset || electrical reset
- Standards
- UL 60947-4-1 || IEC 60947-4-2
- Mounting Support
- DIN rail
- Pollution Degree
- 2
- Net Weight
- 212 g
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV
- Connections - Terminals
- screw clamp terminals 1 0.2-2.5 mm² rigid || screw clamp terminals 1 0.25-2.5 mm² flexible - with cable end || screw clamp terminals 1 0.2-2.5 mm² flexible - without cable end
- Current Consumption
- <= 4 mA 110...230 V AC
- [Ui] Rated Insulation Voltage
- 500 V AC 50/60 Hz
- Mounting Mode
- by clips
- Maximum Operating Rate
- 120 cyc/mn AC-51 50 % || 6 cyc/mn AC-53A 50 %
- Auxiliary Contact Composition
- 1 C/O fault signalling
- Control Circuit Voltage Limits
- 85...253 V AC
- Certifications
- cULus || CE
- Width
- 22.5 mm
- Tightening Torque
- 0.5-0.6 N.m flat Ø 2.5 mm 3 mm
- Depth
- 114.5 mm
- Electrical Durability
- 30 Mcycles
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1509013EN
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1509013EN
- Eu Rohs Directive
- Compliant
Environment
- Ambient Air Temperature For Operation
- -25-30 °C without derating || 30-70 °C with derating
- Ambient Air Temperature For Storage
- -40-80 °C
- Protective Treatment
- TC
- Ip Degree Of Protection
- IP20
Modelos CAD
traceparts
Descargar