- [Us] Rated Supply Voltage
- 24...240 V AC/DC 50/60 Hz +/- 10 %
- Polarity
- yes DC
- Maximum Measuring Cycle
- 30 ms measurement cycle as true rms value
- Control Circuit Voltage Limits
- 15 % + 10 % Un
- Hysteresis
- 15-15 % fixed threshold setting
- Insulation Resistance
- > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
- Measurement Error
- +/- 0.05 %/°C with temperature variation || < 1 % over the whole range with voltage variation
- Operating Rate
- <= 360 operations/hour full load
- Output Contacts
- 1 C/O
- Contacts Material
- cadmium free
- Marking
- CE : 73/23/EEC || CE : EMC 89/336/EEC
- Response Time
- < 200 ms (in the event of a fault)
- Operating Position
- any position without derating
- Input Current
- 100000 mA permanent at 25 °C || 300000 mA non repetitive < 3 s at 25 °C
- Net Weight
- 0.13 kg
- Threshold Setting
- 10...100 %
- Maximum Switching Voltage
- 250 V AC/DC
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 400 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Insulation
- between supply and measurement
- Supply Voltage Limits
- 20.4-264 V AC/DC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for power ON LED (green) || for relay ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Control Circuit Frequency
- 40...70 Hz sinusoidal
- Measurement Accuracy
- +/- 10 % of the full scale value
- Width
- 17.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 1 W
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 0.5 s
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit