Universal plug in relay, Harmony, 10A, 3CO, lockable test button, 125V DC
RUMC31GD
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Oferta con plazo de entrega del fabricante
Entrega:1 - 2 días laborables
El mejor precio:
€4.57

Additional Information

Part Number
RUMC31GD
UNSPSC
39122325
Tariff Code
8536490080
Country of Origin
CN

Offer Sustainability

Rohs Exemption Information
Yes
Environmental Disclosure
ENVPEP1406038EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
China Rohs Regulation
X
Circularity Profile
N/A
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Maximum Switching Capacity
2500 VA/280 W
Safety Reliability Data
B10d = 100000
Operating Rate
<= 18000 cycles/hour no-load || <= 1200 cycles/hour under load
Protection Category
RT I
Test Levels
level A group mounting
Electrical Durability
100000 cycles resistive
Contacts Material
AgNi
Shape Of Pin
cylindrical
Reset Time
20 ms at nominal voltage
Net Weight
0.086 kg
[Uimp] Rated Impulse Withstand Voltage
4 kV 1.2/50 µs)
Maximum Switching Voltage
250 V IEC
Average Resistance
9766 Ohm 20 °C +/- 10 %
Device Presentation
complete product
[Ie] Rated Operational Current
10 A at 277 V AC conforming to UL || 10 A at 30 V DC conforming to UL || 10 A at 277 V AC (same polarity) conforming to CSA || 10 A at 30 V DC conforming to CSA || 5 A at 250 V AC (NC) conforming to IEC || 5 A at 28 V DC (NC) conforming to IEC || 10 A at 250 V AC (NO) conforming to IEC || 10 A at 28 V DC (NO) conforming to IEC
Average Coil Consumption
1.4 W
Rated Operational Voltage Limits
100...137.5 V DC
[Ui] Rated Insulation Voltage
250 V IEC || 300 V CSA || 300 V UL
Mechanical Durability
5000000 cycles
Operating Position
any position
Operating Time
20 ms at nominal voltage
Load Current
10 A 250 V AC || 10 A 28 V DC
Drop-Out Voltage Threshold
>= 0.1 Uc DC
Minimum Switching Capacity
170 mW 10 mA, 17 V

Environment

Product Certifications
CSA || UL || EAC
Standards
UL 508 || IEC 61810-1 || CSA C22.2 No 14
Pollution Degree
2
Ambient Air Temperature For Operation
-40-55 °C
Dielectric Strength
1500 V AC between contacts with micro disconnection || 2500 V AC between coil and contact with reinforced || 2000 V AC between poles with basic
Vibration Resistance
3 gn +/- 1 mm 10-150 Hz)5 cycles in operation || 4 gn +/- 1 mm 10-150 Hz)5 cycles not operating
Shock Resistance
10 gn 11 ms) in operation IEC 60068-2-27 || 10 gn 11 ms) not operating IEC 60068-2-27
Ip Degree Of Protection
IP40
Ambient Air Temperature For Storage
-40-85 °C

Specifications

Utilisation Coefficient
20 %
[Uc] Control Circuit Voltage
125 V DC
Range Of Product
Harmony Electromechanical Relays
Product Or Component Type
plug-in relay
Status Led
without
Control Type
lockable test button
Series Name
Universal
Contacts Type And Composition
3 C/O
Device Short Name
RUM
[Ithe] Conventional Enclosed Thermal Current
10 A -40-55 °C