The SpaceLogic UI-8/DO-FC-4 is a universal input, 8 channel and digital output, 4 channel I/O expansion module for the SpaceLogic AS-P Server. The universal inputs are ideal for any mix of temperature, pressure, flow, status points and similar point types in a building control system. The digital outputs support digital Form C point types designed for direct load applications. The UI-8/DO-FC-4-H I/O expansion module features 8 universal inputs and 4 digital Form C outputs. Its dimensions are 114 mm (4.5 in.) in height, 90 mm (3.6 in.) in width and 64 mm (2.5 in.) in depth. This I/O module requires a SpaceLogic Central I/O Terminal Base (SXWTBIOW110001).
Country of Origin
SE
Part Number
SXWUI8D4X10001
€470.00
net
€500.00
1
Métodos de pago:
Mejor oferta de:
CHProveedor de confianza de Automa.Net
Disponibilidad:
2 piezas
En stock
Actualizado en: 08-11-2024
Garantía:
6 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Un total de 4 Parts In-Stock de 1 Distributor
Información de envío
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Ofertas Disponibles (1)

SXWUI8D4X10001 product image
Schneider Electric

SXWUI8D4X10001

Condición:
Usado
Disponible:
2 piezas
En stock
Actualizado en: 08-11-2024
Oferta de:
CHProveedor de confianza de Automa.Net
Entrega Estimada:
Bajo pedido
Garantía:
3 meses
1
€380.00
€357.20
net

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1611005
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1611005
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts & cables product

Specifications

Product Certifications
ICES-003 || FCC part 15 class B || CE || RCM
Product Brand
Schneider Electric
Ambient Air Temperature For Operation
0-50 °C
Height
114 mm
Product Or Component Type
I/O module
Input/Output Type
universal input
Product Name
I/O Modules
Net Weight
181 g
Range
EcoStruxure Building Operation
Flame Retardance
UL94V0-5VB
Ambient Air Temperature For Storage
-20-70 °C
Power Consumption In Va
1.9 W
Relative Humidity
0-95 % non-condensing
Width
30 mm
Depth
64 mm
Device Short Name
UI-8/DO-FC-4
Ip Degree Of Protection
IP20

Complementary

Discrete Output Type
relay
Switching Frequency
25 Hz
Discrete Input Voltage
24 V
Mounting Support
wall || DIN rail
Standards
UL 864 || UL 916 || FCC CFR 47 part 15
Range Compatibility
EcoStruxure Building Operation TB-IO-W1 terminal base
Local Signalling
LED green/red) high signal level || LED green/red) low signal level
Control Type
Without
Discrete Output Number
4
Discrete Input Number
8
Material
ABS + PC
Electrical Connection
plug-in sub-base
Product Compatibility
Honeywell || Xenta || Continuum || Satchwell || Johnson Control || I/NET || Balco
Analogue Input Type
configurable voltage, current or probe 0...20 mA || configurable voltage, current or probe 0...10 V input voltage || configurable voltage, current or probe 20 kOhm connection of probes || configurable voltage, current or probe 10 kOhm connection of probes || configurable voltage, current or probe 2.2 kOhm connection of probes || configurable voltage, current or probe 1.8 kOhm connection of probes || configurable voltage, current or probe 1 kOhm connection of probes || configurable voltage, current or probe 10 kOhm with shunt

Documentos

Data Sheet

Descargar