- Maximum Cable Distance Between Devices
- twisted shielded pairs cable <30 m input
- Electrical Connection
- 1 x 1.5 mm² 1 spring terminal block pitch 3.81 mm for outputs and supply
- Height
- 50 mm
- Input Impedance
- >= 1 MOhm
- Non-Linearity
- +/- 0.05 %FS
- Lsb Value
- 0.1 °C
- Permissible Continuous Overload
- 6 V
- Analogue Input Resolution
- 14 bits
- Net Weight
- 0.055 kg
- Type Of Cable
- twisted shielded pairs cable
- Absolute Accuracy Error
- +/- 0.5 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe || +/- 0.2 % of full scale at 25 °C for thermocouple K - 200...1300 °C || +/- 0.2 % of full scale at 25 °C for thermocouple J - 200...1000 °C || +/- 0.2 % of full scale at 25 °C for thermocouple E - 200...800 °C || +/- 0.2 % of full scale at 25 °C for thermocouple T - 200...400 °C || +/- 0.2 % of full scale at 25 °C for thermocouple N - 200...1300 °C || +/- 0.2 % of full scale at 25 °C for thermocouple B 250...400 °C || +/- 0.1 % of full scale at 25 °C for thermocouple B 400...1280 °C || +/- 0.2 % of full scale at 25 °C for thermocouple R, S 0...1760°C
- Temperature Drift
- +/- 0.008 %FS/°C
- Supply Voltage Limits
- 20.4-28.8 V
- Local Signalling
- for PWR 1 LED (green)
- Cross Talk
- 80 dB
- Width
- 34 mm
- Depth
- 21 mm
- Insulation
- between input and internal logic 500 V DC || non-insulated between inputs
- Sampling Duration
- 100 ms
- Repeat Accuracy
- +/- 0.1 %FS
- Analogue Input Type
- thermocouple - 200...1000 °C thermocouple J || Pt 100 temperature probe - 200...850 °C || Pt 1000 temperature probe - 200...600 °C || thermocouple - 200...1300 °C thermocouple K || thermocouple 0...1760 °C thermocouple R || thermocouple 0...1760 °C thermocouple S || thermocouple 0...1820 °C thermocouple B || thermocouple - 200...400 °C thermocouple T || thermocouple - 200...1300 °C thermocouple N || thermocouple - 200...800 °C thermocouple E || Ni 100/Ni 1000 temperature probe - 60...180 °C