Schneider Electric
XB6AE4B5B
1 / 1
Descripción
Activo maduro
- Country of Origin
- FR
- Part Number
- XB6AE4B5B
- Tariff Code
- 85365080
- EAN
- 3389110764161
- UNSPSC
- 39122216
Métodos de pago:
- Mejor oferta de:
- Proveedor de confianza de Automa.Net
- Disponibilidad:
- 1 piezaEn stockActualizado en: 08-11-2024
- Garantía:
- 12 meses
- Entrega Estimada:
- Bajo pedido
- Condición:
- Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía
Specifications
- Range Of Product
- Harmony XB6
- Light Source
- LED
- Mounting Diameter
- 16 mm
- Type Of Operator
- spring return
- Product Or Component Type
- complete illuminated push-button
- Shape Of Signaling Unit Head
- round
- Connections - Terminals
- Faston connectors 2.8 x 0.5 mm
- Contacts Type And Composition
- 1 NO + 1 NC
- Sale Per Indivisible Quantity
- 1
- Bezel Material
- plastic
- Contact Operation
- slow-break
- Operator Profile
- red projecting, unmarked
- Device Short Name
- XB6
- [Us] Rated Supply Voltage
- 12...24 V AC/DC
- Bulb Base
- integral LED
Contractual warranty
- Warranty
- 18 months
Complementary
- Terminals Description Iso N°1
- (21-22)NC || (13-14)NO
- Short-Circuit Protection
- 6 A cartridge fuse gG
- Operating Force
- 3.5 N NO changing electrical state || 4.5 N NC changing electrical state
- Operating Travel
- 1 mm NO changing electrical state) || 2 mm NC changing electrical state) || 3.5 mm total travel)
- Contacts Material
- silver alloy (Ag/Ni)
- Positive Opening
- with EN/IEC 60947-5-1 appendix K
- Net Weight
- 0.025 kg
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV EN/IEC 60947-1
- Cad Overall Height
- 18 mm
- Current Consumption
- 15 mA
- Electrical Durability
- 1000000 cycles, AC-15 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
- Surge Withstand
- 1 kV direct contact IEC 61000-4-5 || 2 kV in free air IEC 61000-4-5
- [Ui] Rated Insulation Voltage
- 250 V 3)EN/IEC 60947-1
- Signalling Type
- steady
- [Ie] Rated Operational Current
- 3 A 120 V, AC-15, B300 EN/IEC 60947-5-1 || 1.5 A 240 V, AC-15, B300 EN/IEC 60947-5-1 || 0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1 || 0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1
- Supply Voltage Limits
- 6-30 V AC/DC
- Operating Position
- any position
- Electrical Reliability
- λ = 10exp(-8) 5 V 1 mA with confidence level of 90 % IEC 60947-5-4
- Cad Overall Width
- 18 mm
- Cad Overall Depth
- 61 mm
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1710010EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1710010EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Environment
- Product Certifications
- CCC || CSA || UL || GOST
- Ambient Air Temperature For Operation
- -25-70 °C
- Resistance To Electromagnetic Fields
- 10 V/m IEC 61000-4-3
- Standards
- CSA C22.2 No 14 || JIS C 4520 || EN/IEC 60947-1 || JIS C 852 || EN/IEC 60947-5-1 || EN/IEC 60947-5-5
- Shock Resistance
- 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
- Vibration Resistance
- +/- 3 mm 2-500 Hz)IEC 60068-2-6 || 5 gn 2-500 Hz)IEC 60068-2-6
- Ip Degree Of Protection
- IP65 IEC 60529
- Ambient Air Temperature For Storage
- -40-70 °C
- Nema Degree Of Protection
- NEMA 13 UL 50 || NEMA 4 UL 50 || NEMA 4X UL 50 || NEMA 13 CSA C22.2 No 94 || NEMA 4 CSA C22.2 No 94 || NEMA 4X CSA C22.2 No 94
- Resistance To Electrostatic Discharge
- 6 kV on contact (on metal parts) IEC 61000-4-2 || 8 kV in free air (in insulating parts) IEC 61000-4-2
- Electrical Shock Protection Class
- class II IEC 61140
- Protective Treatment
- TC
- Resistance To Fast Transients
- 2 kV IEC 61000-4-4
- Electromagnetic Emission
- class B IEC 55011
Otras categorías
ActuadoresBloquesCables, tuberías y manguerasCompresoresControlAcoplamientos y AccesoriosCilindros y PistonesElectrónicaFiltrosHVACPCs industriales y HMIsIluminaciónTécnica linealMotoresFuente de alimentaciónTransmisión de energíaBombas y VálvulasEnergías renovablesRobóticaSellos, anillos y conectoresSensores y dispositivos de mediciónHerramientas y AccesoriosCNCOtros