- Communication
- Modbus (TCP, UDP) || ETHERNET || EtherNet/IPTM Adapter (slave), library for e!RUNTIME || Modbus® RTU || RS-232 serial interface || RS-485 interface || MQTT || Telecontrol protocols
- ETHERNET protocols
- DHCP || DNS || NTP || FTP || FTPS || SNMP || HTTP || HTTPS || SSH
- Telecontrol protocols
- IEC 60870-5-101/-103/-104 || IEC 61400-25 || IEC 61850-7 || DNP3
- Visualization
- Web-Visu
- Operating system
- Real-time Linux (with RT-Preempt patch)
- CPU
- Cortex A8; 600 MHz
- Programming languages per IEC 61131-3
- Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD) || Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
- Programming environment
- e!COCKPIT (based on CODESYS V3) || WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
- Configuration options
- e!COCKPIT || WAGO-I/O-CHECK || Web-Based Management || e!RUNTIME library || CODESYS Library
- Baud rate (communication/fieldbus 1)
- 10/100 Mbit/s
- Baud rate
- ETHERNET: 10/100 Mbit/s
- Transmission medium (communication/fieldbus)
- ETHERNET: Twisted pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
- Main memory (RAM)
- 256 MB
- Internal memory (flash)
- 256 MB
- Non-volatile hardware memory
- 128 KB
- Program memory
- CODESYS V2: 16 MB; CODESYS V3: 60 MB (Program and data memory (dynamically distributed))
- Data memory
- CODESYS V2: 64 MB; CODESYS V3: 60 MB Program and data memory (dynamically distributed)
- Non-volatile software memory
- 128 KB || 128 KB
- Type of memory card
- SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO Memory Card)
- Memory card slot
- Push-push mechanism; cover lid (sealable)
- Number of modules per node (max.)
- 64
- Input and output process image (internal) max.
- 1000 words/1000 words
- Input and output process image (Modbus®) max.
- CODESYS V2: 1000 words/1000 words; CODESYS V3: 32000 words/32000 words
- Indicators
- LED (SYS, RUN, I/O, U1 … U7) red/green/orange: Status of system, program, local data bus, status programmable by user (can be used via CODESYS library); LED (A, B) green: Status of system power supply, field supply
- Derating
- Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
- Supply voltage (system)
- 24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed!
- Input current (typ.) at nominal load (24 V)
- 550 mA
- Power supply efficiency (typ.) at nominal load (24 V)
- 90 %
- Current consumption (5 V system supply)
- 510 mA
- Total current (system supply)
- 1700 mA
- Supply voltage (field)
- 24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed!
- Current carrying capacity (power jumper contacts)
- 10 A
- Number of outgoing power jumper contacts
- 2
- Ratings per
- IEC/EN 60664-1
- Rated surge voltage
- 1 kV