Wago

855-9150/2000-1251

Rogowski coil; RT 4000; Diameter 125 mm; 1.5 m; Bayonet connector; for cable tie
855-9150/2000-1251
855-9150/2000-1251
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:

Additional Information

Part Number
855-9150/2000-1251
UPC
4055143419208
Tariff Code
90303370000
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Current transformer
Class Code : EC002048
Version : 7

Output (Analog)

Sensitivity
22.5 mV/kA at 50 Hz
Output signal (max.)
30 V

Signal Processing

Limit frequency
373 kHz

Environmental Requirements

Ambient temperature (operation)
-40 … +80 °C
Ambient temperature (storage)
-40 … +80 °C
Relative humidity
≤ 90% (without condensation)
Operating altitude (max.)
2000 m

Connection Data

Feedthrough for measurement conductor
Ø 125 mm

Physical Data

Cable length
1.5 m

Measurement Error

Accuracy class
0.5
Translation errors (all positions)
0.75 %
Translation errors (note)
Assuming that a primary conductor with a minimum diameter of 15 mm is used that is routed perpendicular to and in contact with the coil.

Material Data

Fire load
0.000 MJ
Weight
130.000 g

Input

Measurement range
10 A ... 10000 A (up to 4000 A in combination with the recommended WAGO products)

Input Current Transformers

Primary rated current
1000 A
Rated short-time thermal current Ith
300 kA at 50 Hz
Rated frequency
50 … 60 Hz
Mutual inductance M
72.14 nH

Standards And Specifications

Conformity marking
CE
Standards/specifications
EN 61010-1 || EN 61010-2-32 || EN 61869-1 || EN 61869-2 || EN 61869-6 || EN 61869-10 || UL 61010-1

Mechanical Data

Mounting type
Split-core current transformer (suspended)

Specifications

Product Group Code
0029

Commercial Data

Packaging type
Bag
Country of origin
CH
GTIN
4055143419208
Customs tariff number
90303370000

Notes

Note
Rogowski technology allows the coils to measure a wide primary current range of up to 10,000 A without loss of accuracy, because there are no saturation effects. The requirements for standards EN 61869-1, EN 61869-2, EN 61869-6 and EN 61869-10 are only partially met, as there are fundamental differences with current transformers for a Rogowski coil.

Test Voltage

Voltage for isolation test
AC 7.4 kV; 50 Hz; 1 min