ABB
1SFL467001R1111
AF146-30-11-11 Contactor
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
$909.33
1
Metodi di pagamento:
Un totale di 303 Parts In-Stock da 17 Distributors
Condizioni del prodotto:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€226.09
Additional Information
- Part Number
- 1SFL467001R1111
- UPC
- 73205004820560
- UNSPSC
- 39121529
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power contactor, AC switching
- Class Code : EC000066
- Version : 7
Dimensions
- Product Net Width
- 90 mm
- Product Net Depth / Length
- 126 mm
- Product Net Height
- 150 mm
- Product Net Weight
- 1.55 kg
Technical
- Number of Main Contacts NO
- 3
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 1
- Number of Auxiliary Contacts NC
- 1
- Rated Operational Voltage
- Main Circuit 1000 V
- Rated Frequency (f)
- Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 225 A
- Rated Operational Current AC-1 (Ie)
- (1000 V) 40 °C 225 A(1000 V) 55 °C 200 A(1000 V) 60 °C 200 A(1000 V) 70 °C 175 A(690 V) 40 °C 225 A(690 V) 55 °C 200 A(690 V) 60 °C 200 A(690 V) 70 °C 175 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 55 °C 146 A(440 V) 55 °C 146 A(500 V) 55 °C 130 A(690 V) 55 °C 93 A(1000 V) 55 °C 60 A(380 / 400 V) 55 °C 146 A(220 / 230 / 240 V) 55 °C 146
- Rated Operational Current AC-3e (Ie)
- (415 V) 60 °C 146 A(440 V) 60 °C 146 A(500 V) 60 °C 130 A(690 V) 60 °C 93 A(1000 V) 60 °C 54 A(380 / 400 V) 60 °C 146 A(220 / 230 / 240 V) 60 °C 146 A
- Rated Operational Power AC-3 (Pe)
- (415 V) 75 kW(440 V) 90 kW(500 V) 90 kW(690 V) 90 kW(1000 V) 75 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 45 kW
- Rated Operational Power AC-3e (Pe)
- (415 V) 75 kW(440 V) 90 kW(500 V) 90 kW(690 V) 90 kW(1000 V) 75 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 45 kW
- Rated Breaking Capacity AC-3
- 8 x Ie AC-3
- Rated Breaking Capacity AC-3e
- 8.5 x Ie AC-3e
- Rated Making Capacity AC-3
- 10 x Ie AC-3
- Rated Making Capacity AC-3e
- 12 x Ie AC-3e
- Short-Circuit Protective Devices
- gG Type Fuses 315 A
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
- Maximum Electrical Switching Frequency
- (AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 8 kV
- Mechanical Durability
- 5 million
- Maximum Mechanical Switching Frequency
- 300 cycles per hour
- Coil Operating Limits
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
- Rated Control Circuit Voltage (Uc)
- 50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V
- Coil Consumption
- Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·AHolding at Max. Rated Control Circuit Voltage DC 2.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·APull-in at Max. Rated Control Circuit Voltage DC 210 W
- Operate Time
- Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms
- Connecting Capacity Main Circuit
- Flexible 2 x 10 ... 70 mm²Rigid Cu-Cable 2 x 10 ... 95 mm²
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 1 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type
- Double Clamp
Eco Transparency
- Environmental Product Declaration - EPD
- 1SFC100092D0201
Classifications
- Object Classification Code
- Q
- ETIM 4
- EC000066 - Magnet contactor, AC-switching
- ETIM 5
- EC000066 - Magnet contactor, AC-switching
- EClass
- V11.0 : 27371003
- IDEA Granular Category Code (IGCC)
- 4758 >> Iec Contactors
- E-Number (Finland)
- 3706364
- E-Number (Norway)
- 4117630
Environmental
- Ambient Air Temperature
- Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Circular Value
- ABB EcoSolutions
- Yes
- Circular Design Principles Recyclability Rate
- Design for Closing Resource Loops - Standard EN45555 - 87.8 %
- End of Life Instructions
- 1SFC100112M0001
- Group Waste to Landfill Target
- Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
- Improved Resource Efficiency for Customers
- Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
- Sustainable Material Content
- Recycled Metal - 37 %
Technical UL/CSA
- Maximum Operating Voltage UL/CSA
- Main Circuit 1000 V
- General Use Rating UL/CSA
- (600 V AC) 200 A
- Horsepower Rating UL/CSA
- (200 V AC) Three Phase 40 hp(208 V AC) Three Phase 40 hp(220 ... 240 V AC) Three Phase 50 hp(440 ... 480 V AC) Three Phase 100 hp(550 ... 600 V AC) Three Phase 125 hp
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900